Setting menu 1: Phase wire system, primary voltage, primary current, demand time, etc.
In this menu, set phase wire system, primary voltage, primary current, demand time, etc.
In operating mode, press both and at the same time for more than two seconds to transition to setting
mode and enable the following operations.
(3) Primary voltage
(Direct)
Set the direct voltage according to voltage of the measured circuit
・
In case you choose “3P4”in (1) Phase wire system
・
In case you choose “3P3” or “1P2”in (1) Phase wire system
63.5V/110V
100V/173V
105V/182V
110V/190V
115V/199V
120V/208V
127V/220V
200V/346V
220V/380V
230V/400V
240V/415V
242V/420V
250V/430V
254V/440V
265V/460V
277V/480V
110V 220V 440V
Setting menu
Choose the setting menu 1.
(As shown in the left figure)
(1) Phase wire system
Set according to the phase wire system for the measured circuit.
3P4: Three-phase 4-wire
1P2: Single-phase 2-wire
1P3: Single-phase 3-wire
3P3: Three-phase 3-wire
Supplement: The underlined values are the defaults. (The same shall apply hereinafter.)
(2) Primary voltage
(Use or non-use of VT)
If you measure directly (i.e. without VT):
→
Choose “no” and press to transition to (3) Primary voltage (Direct).
If you measure with VT:
→
Choose “yES” and press to transition to (4) Primary voltage (VT).
no
Supplement:
“VT” means Voltage Transformer.
SET
SET
<In case you choose “1P3” in (1) Phase wire system>
You can use direct measurement only.
Setting of primary voltage is skipped and setting is started
from (7) Primary current
Rated voltage between 1- and 2-phase and 2- and 3-phase is
110V, and that between 1- and 3-phase is 220V.
yES
- / RESET
SET
SET
DISP
DISP
SET
SET
DISP
SET
DISP