background image

9

GB

D

F

I

NL

E

P

GR

RU

TR

2

Water quality standard

Reference : Guideline of Water Quality for Refrigeration and Air Conditioning

Equipment. (JRA GL02E-1994)

3

Please consult with a water quality control specialist about water quality
control methods and water quality calculations before using anti-corrosive
solutions for water quality management.

4

When replacing a previously installed air conditioning device (even when
only the heat exchanger is being replaced), first conduct a water quality
analysis and check for possible corrosion.
Corrosion can occur in cold-water systems even if there has been no prior
signs of corrosion.
If the water quality level has dropped, please adjust water quality suffi-
ciently before replacing the unit.

7.4. Pump interlock

The heat source unit may become damaged if it is operated with no water circulat-
ing through the pipes.
Be sure to interlock unit operation and the water-circuit pump. Use the terminal
blocks for interlocking (TB8-3, 4) that can be found on the unit.
In the case of a pump interlock circuit signal connection to the TB8-3, 4, remove
the short-circuit wire. Also, to prevent mistaken error detection, resulting from a
poor connection, in the pressure valve 63PW, use a low maintained current of 5mA
or less.

[Fig. 7.4.1] (P.2)

A

Short-circuit wire (Connected before delivery from manufacturer)

B

Pump interlock circuit connection

pH (25˚C) [77

°

F]

Electric conductivity (mS/m) (25

°

C) [77

°

F]

(

µ

 s/cm) (25

°

C) [77

°

F]

Chloride ion

(mg Cl

-

/

r

)

Sulfate ion

(mg SO4

2-

/

r

)

Acid consumption (pH4.8)

 

(mg CaCO

3

/

r

)

Total hardness

(mg CaCO

3

/

r

)

Calcium hardness (mg CaCO

3

/

r

)

Ionic silica

(mg SiO

2

/

r

)

Iron

(mg Fe/

r

)

Copper

(mg Cu/

r

)

Sulfide ion

(mg S

2-

/

r

)

Ammonium ion

(mg NH

4

+

/

r

)

Residual chlorine

(mg Cl/

r

)

Free carbon dioxide

(mg CO

2

/

r

)

Ryzner stability index

Standard

items

Refer-

ence

items

Items

Lower mid-range

temperature water system

7.0 ~ 8.0

30 or less

[300 or less]

50 or less

50 or less

50 or less

70 or less

50 or less

30 or less

1.0 or less

1.0 or less

not to be

detected

0.3 or less

0.25 or less

0.4 or less

7.0 ~ 8.0

30 or less

[300 or less]

50 or less

50 or less

50 or less

70 or less

50 or less

30 or less

0.3 or less

0.1 or less

not to be

detected

0.1 or less

0.3 or less

4.0 or less

Tendency

Recirculating

water

[20<T<60

°

C]

[68<T<140

°

F]

Make-up

water

Corrosive

Scale-

forming

8. Refrigerant piping installation

A

Residues in commercially available antioxidants may have adverse effects on
the equipment. Braze only with non-oxide brazing material. The use of other
brazing material may result in compressor damage.
(Refer to item 9.2. for detailed information on pipe connections and valve op-
erations.)

B

Never perform heat source unit piping connection work when it is raining.

 Warning

When installing and moving the unit, do not charge it with refrigerant other
than the refrigerant specified on the unit.

- Mixing of a different refrigerant, air, etc. may cause the refrigerant cycle to mal-

function and result in severe damage.

 Caution:

Use a vacuum pump with a reverse flow check valve.

- If the vacuum pump does not have a reverse flow check valve, the vacuum

pump oil may flow back into the refrigerant cycle and cause deterioration of
the refrigerator oil and other trouble.

Do not use the tools shown below used with conventional refrigerant.
(Gauge manifold, charge hose, gas leak detector, check valve, refrigerant
charge base, vacuum gauge, refrigerant recovery equipment)

- Mixing of conventional refrigerant and refrigerator oil may cause the refrig-

erator oil to deteriorate.

- Mixing of water will cause the refrigerator oil to deteriorate.
- R410A refrigerant does not contain any chlorine. Therefore, gas leak detec-

tors for conventional refrigerants will not react to it.

Manage the tools more carefully than normal.

- If dust, dirt, or water gets in the refrigerant cycle, the refrigerator oil will dete-

riorate.

Never use existing refrigerant piping.

- The large amount of chlorine in conventional refrigerant and refrigerator oil

in the existing piping will cause the new refrigerant to deteriorate.

Store the piping to be used during installation indoors and keep both
ends of the piping sealed until just before brazing.

- If dust, dirt, or water gets into the refrigerant cycle, the oil will deteriorate and

the compressor may fail.

Do not use a charging cylinder.

- Using a charging cylinder may cause the refrigerant to deteriorate.

Do not use special detergents for washing piping.

8.2. Refrigerant piping system

Connection Example

[Fig. 8.2.1]

 

(P.3)

Å

Heat source model

ı

 Liquid pipe

Ç

Gas pipe

Î

Total capacity of indoor units

Model number

Ï

Downstream unit model total

Ì

Branch kit model

Ó

4-Branching header (Downstream unit model total 

<

=

 200)

¬

8-Branching header (Downstream unit model total 

<

=

 400)

Ô

10-Branching header (Downstream unit model total 

<

=

 650)

A

Heat source unit

B

First branch

C

Indoor unit

D

Cap

Connecting the piping is a terminal-branch type in which refrigerant piping from
the heat source unit is branched at the terminal and connected to each of the
indoor units.
The method of pipe connection is as follows: flare connection for the indoor units, gas
pipes for heat source units, flare connection for P72 and brazed connection for P96 ~
P168; liquid pipes, flare connection. Note that the branched sections are brazed.

 Warning:

Always use extreme care to prevent the refrigerant gas from leaking while
using fire or flame. If the refrigerant gas comes in contact with a flame from
any source, such as a gas stove, it breaks down and generates a poisonous
gas which can cause gas poisoning. Never weld in an unventilated room.
Always conduct an inspection for gas leakage after installation of the refrig-
erant piping has been completed.

8.1. Caution

This unit uses refrigerant R410A. Follow the local regulations on materials and
pipe thickness when selecting pipes.

1

Use the following materials for refrigeration piping.

Material: Use refrigerant piping made of phosphorus deoxidized copper.
In addition, be sure that the inner and outer surfaces of the pipes are clean
and free of hazardous sulphur, oxides, dust/dirt, shaving particles, oils,
moisture, or any other contaminant.

2

Commercially available piping often contains dust and other materials.  Always
blow it clean with a dry inert gas.

3

Use care to prevent dust, water or other contaminants from entering the piping
during installation.

4

Reduce the number of bending portions as much as possible, and make bend-
ing radius as big as possible.

5

Always observe the restrictions on the refrigerant piping (such as rated length,
the difference between high/low pressures, and piping diameter).  Failure to do
so can result in equipment failure or a decline in heating/cooling performance.

6

Either a lack or an excess of refrigerant causes the unit to make an emergency
stop. Charge the system with an appropriate amount of refrigerant. At such a
time, always properly charge the unit.  When servicing, always check the notes
concerning pipe length and amount of additional refrigerant at both locations,
the refrigerant volume calculation table on the back of the service panel and
the additional refrigerant section on the labels for the combined number of
indoor units.

7

Use liquid refrigerant to fill the system.

8

Never use refrigerant to perform an air purge.  Always evacuate using a vacuum
pump.

9

Always insulate the piping properly.  Insufficient insulation will result in a de-
cline in heating/cooling performance, water drops from condensation and other
such problems.

0

When connecting the refrigerant piping, make sure the ball valve of the heat
source unit is completely closed (the factory setting) and do not operate it until
the refrigerant piping for the heat source and indoor units has been connected,
a refrigerant leakage test has been performed and the evacuation process has
been completed.

Summary of Contents for CITY MULTI PQHY-P72TGMU-A

Page 1: ...r safe and correct use please read this installation manual thoroughly before installing the air conditioner unit MANUEL D INSTALLATION Veuillez lire le manuel d installation en entier avant d installer ce climatiseur pour éviter tout accident et vous assurer d une utilisation correcte For use with R410A ...

Page 2: ...4 ø14 9 16 Anchoring hole C Top view A Piping space for side piping B Heat source unit C Service space front side D Top view D Anti vibration pad etc E Concrete base E Piping space for top piping F Piping space for side piping G Heat source unit H Front view A Water circulation pipe B Close valve C Close valve D Water outlet A Short circuit wire Connected before delivery from manufacturer B Pump i...

Page 3: ...2 ø15 88 5 8 ø19 05 3 4 ø22 2 7 8 Ó 4 Branching header Downstream unit model total 200 CMY Y104 G 8 Branching header Downstream unit model total 400 CMY Y108 G Ô 10 Branching header Downstream unit model total 650 CMY Y1010 G Ï Downstream unit model total 72 73 400 Ì Branch kit model CMY Y102S G CMY Y102L G Fig 9 2 2 9 2 9 Fig 9 2 1 A B 1 3 A Ball valve Low press side flanged type B Ball valve Hig...

Page 4: ... material C Lagging D Caulking material E Band F Waterproofing laye G Sleeve with edge H Lagging material I Mortar or other incombustible caulking J Incombustible heat insulation material A Power source B Transmission line C Ground screw D C C B B E F G H I J A LO HI LO HI B A K J L H M C D E N O F G I Fig 9 3 1 Fig 9 3 3 Fig 9 3 2 9 3 A A Nitrogen gas B To indoor unit C System analyzer D Lo knob ...

Page 5: ... M1M2S TB5 07 IC M1M2S TB5 06 L 2 L1 MA MA MA OC M1M2 M1M2S TB7 TB3 52 OC c 1 c4 S System controller L3 L 6 L4 c 2 A B A B A B A B M1M2 c 2 c 1 c 1 c2 CN40 CN40 c 3 10 3 B A C 208 230 V B A 208 230 V E E D E E Fig 10 3 2 Fig 10 3 1 A Group 1 B Group 3 C Group 5 D Shielded wire E Sub remote controller Address A Change the jumper connec tor from CN41 to CN40 B SW2 1 ON C Keep the jumper connector on...

Page 6: ...to be exceeded hazards due to lack of oxygen in the room could result When moving and reinstalling the air conditioner consult the dealer or an authorized technician If the air conditioner is installed improperly water leakage electric shock or fire may result After completing installation work make sure that refrigerant gas is not leaking If the refrigerant gas leaks and is exposed to a fan heate...

Page 7: ... valve The vacuum pump oil may flow back into the refrigerant cycle and cause the refrigerator oil to deteriorate Do not use the following tools that are used with conventional refriger ants Gauge manifold charge hose gas leak detector reverse flow check valve refrigerant charge base refrigerant recovery equipment If the conventional refrigerant and refrigerator oil are mixed in the R410A the refr...

Page 8: ... excess air Compressed water may form in the low temperature sections of heat source unit Use a drainage pipe connected to the drain valve at the base of the unit to drain the water There is a water vent plug in the center of the heat exchanger water inlet head at the middle of the unit Use this for maintenance etc In addition do not allow any of the unit s electrical parts such as the solenoid va...

Page 9: ...erator oil will dete riorate Never use existing refrigerant piping The large amount of chlorine in conventional refrigerant and refrigerator oil in the existing piping will cause the new refrigerant to deteriorate Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing If dust dirt or water gets into the refrigerant cycle the oil wi...

Page 10: ...orque by torque wrench Copper pipe external dia mm in Tightening torque N m kg cm ø6 35 1 4 14 to 18 140 to 180 ø9 52 3 8 35 to 42 350 to 420 ø12 7 1 2 50 to 57 5 500 to 575 ø15 88 5 8 75 to 80 750 to 800 ø19 05 3 4 100 to 140 1000 to 1400 Tightening angle standard Pipe diameter mm in Tightening angle ø6 35 1 4 ø9 52 3 8 60 to 90 ø12 7 1 2 ø15 88 5 8 30 to 60 ø19 05 3 4 20 to 35 Fig 9 2 3 P 3 flar...

Page 11: ...ic refriger ant R410A gas leakage causes the composition to change and affects perform ance Therefore perform the airtightness test cautiously Caution Only use refrigerant R410A The use of other refrigerant such as R22 or R407C which contains chlorine will deteriorate the refrigerating machine oil or cause the compressor to malfunction 2 Evacuation Evacuate with the ball valve of the heat source u...

Page 12: ...heat source units whose power supply connector CN41 has been replaced by CN40 the shield terminal S of terminal block TB7 of the central control system should also be connected to the ground screw Fix the wiring securely in place with the cable strap at the bottom of the termi nal block so that the external force if not applied to the terminal block External force applied to the terminal block may...

Page 13: ...A Change the jumper connector from CN41 to CN40 B SW2 1 ON C Keep the jumper connector on CN41 A Group 1 B Group 4 C Group 5 D Shielded wire E Sub remote controller Address Wiring Method and Address Settings a Always use shielded wire when making connections between the heat source unit OC and the indoor unit IC as well for all OC OC and IC IC wiring intervals b Use feed wiring to connect terminal...

Page 14: ...light rain water etc when proceeding with the wiring and connections 3 The wire size is the minimum value for metal conduit wiring The power cord size should be 1 rank thicker consideration of voltage drops Make sure the power supply voltage does not drop more than 10 4 Specific wiring requirements should adhere to the wiring regulations of the region 5 Power supply cords of parts of appliances fo...

Page 15: ...rent utilisez le réfrigérant R410A spécifié sur l appareil Lorsqu un réfrigérant différent est mélangé au réfrigérant d origine il se peut que le cycle du réfrigérant ne fonctionne pas correctement et que l appareil soit endommagé Si le climatiseur est installé dans une pièce relativement petite certaines mesures doivent être prises pour éviter que la concentration de réfrigé rant ne dépasse le se...

Page 16: ...nterventions techniques Si l appareil est raccordé au secteur sans fonctionner le chauffage du carter est toujours sous tension au niveau du compresseur 1 2 Précautions à prendre avec les dispo sitifs utilisant le réfrigérant R410A Précaution N utilisez pas les tuyaux de réfrigérant actuels Le vieux réfrigérant et l huile réfrigérante se trouvant dans les tuyaux con tiennent une large quantité de ...

Page 17: ...e il est conseillé de monter une base anti vibrations sur le socle de support de l appareil Fig 6 1 2 P 2 D Coussinet anti vibrations etc E Socle en béton Avertissement Installez toujours l appareil dans un endroit pouvant supporter son poids Dans le cas contraire l appareil pourrait tomber et par conséquent bles ser quelqu un Effectuez les travaux nécessaires afin d assurer a protection de l appa...

Page 18: ...iez que le niveau d oxygène dissous de l eau ne dépasse pas 1 mg r 2 Norme de qualité de l eau Référence Guideline of Water Quality for Refrigeration and Air Conditioning Equipment Directive relative à la qualité de l eau pour le matériel de réfrigération et de climatisation JRA GL02E 1994 3 Contacter un spécialiste du contrôle de la qualité des eaux pour en savoir plus sur les méthodes de contrôl...

Page 19: ...els Jauge collectrice tuyau flexible de remplissage détecteur de fuites de gaz valve de contrôle base de remplissage de réfrigérant jauge à vide équipements de récupération de réfrigérant Il se peut que l huile réfrigérante se détériore à la suite du mélange d un réfrigérant traditionnel à l huile réfrigérante Il se peut que l huile se détériore si de l eau y est mélangée Le réfrigérant R410A ne c...

Page 20: ...9 1 13 2 16 6 19 7 24 0 dimension de l évasement mm taille de l écrou évasé mm diamètre extérieur ø6 35 ø9 52 ø12 70 ø15 88 ø19 05 taille en pouces 1 4 3 8 1 2 5 8 3 4 dimension B R410A 17 0 22 0 26 0 29 0 36 0 Fig 9 2 2 P 3 A Soupape à bille Côté gaz raccordement à brides B Soupape à bille Côté liquide raccordement évasé C Cette figure montre la soupape complètement ouverte A Tige de la valve Ent...

Page 21: ...istor ROBINAIR 14830A Utiliser également une jauge à vide pouvant atteindre 65 Pa abs 0 00943 psi 0 5 Torr maximum après cinq minutes d utilisation 3 Ajout du réfrigérant Etant donné que le réfrigérant utilisé dans cet appareil est nonazéotropique il doit être dans un état liquide lorsqu ajouté Par conséquent lorsque vous char gez l appareil de réfrigérant à l aide d un cylindre si celui ci n est ...

Page 22: ...ls source de chaleur ou le câblage avec le système de contrôle centralisé au bloc de terminaux de le contrôle centralisé TB7 Lors de l utilisation de câblage blindé raccordez la terre blindée de la ligne de transmission de l appareil intérieur à la vis de terre et raccordez la terre blindée de la ligne située entre les appareils source de chaleur et la ligne de transmission du système de contrôle ...

Page 23: ... M2 et à la borne S des câbles de transmission du bloc de l appareil intérieur IC c Raccorder les bornes 1 M1 et 2 M2 du bloc terminal des câbles de transmission de l appareil intérieur IC qui possède l adresse la plus récente au sein d un même groupe au bloc terminal de la commande à distance RC d Raccordez les bornes M1 M2 et la borne S du bloc de terminaux pour le contrôle centralisé TB7 sur l ...

Page 24: ...jusqu à ce que la température des tuyaux atteigne 35 C 95 F il fonctionne lentement pendant les 2 minutes qui suivent puis il fonctionne selon le préréglage Commande de réglage de la chaleur Le système est en train d être mis en marche Utilisez de nouveau la télécommande lorsque HO ou PLEASE WAIT a dis paru de l affichage Lorsque l appareil s arrête après le mode de refroidissement il continue de ...

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ...HIYODA KU TOKYO 100 8310 JAPAN Please be sure to put the contact address telephone number on this manual before handing it to the customer This product is designed and intended for use in the residential commer cial and light industrial environment Printed in Japan ...

Reviews: