6. Installation of unit and service space

6.1. Installation

Using the anchoring holes shown below, firmly bolt the unit to the base.

[Fig. 6.1.1] (P.2)

A

Heat source unit

B

4-ø14 [9/16] (Anchoring hole)

C

(Top view)

Bases and anti-vibration

Be sure to install unit in a place strong enough to withstand its weight. If the
base is unstable, reinforce with a concrete base.

The unit must be anchored on a level surface. Use a level to check after
installation.

Anti-vibration pads must be placed under the base of the unit.

If the unit is installed near a room where noise is a problem, using an anti-
vibration stand on the base of the unit is recommended.

[Fig. 6.1.2]

 

(P.2)

D

Anti-vibration pad etc.

E

Concrete base

 Warning:

Be sure to install unit in a place strong enough to withstand its weight.
Any lack of strength may cause unit to fall down, resulting in a personal
injury.

Have installation work in order to protect against earthquake.
Any installation deficiency may cause unit to fall down, resulting in a
personal injury.

6.2. Service space

Please allow for the following service spaces after installation.
(All servicing can be performed from the front of the unit)

[Fig. 6.2.1]

 

(P.2)

A

Piping space (for side piping)

B

Heat source unit

C

Service space (front side)

D

(Top view)

[Fig. 6.2.2]

 

(P.2)

E

Piping space (for top piping)

F

Piping space (for side piping)

G

Heat source unit

H

(Front view)

5. Lifting method

[Fig. 5.0.1] (P.2)

 Caution:

Be very careful when carrying the product.

- Do not have only one person to carry product if it is more than 20 kg [46 LBS].
- PP bands are used to pack some products. Do not use them as a mean for transportation because they are dangerous.
- Tear plastic packaging bag and scrap it so that children cannot play with it. Otherwise plastic packaging bag may suffocate children to death.
- When carrying the heat source unit, be sure to support it at four points. Carrying with 3-point support may make the heat source unit unstable, resulting in it falling.

4. Confirmation of parts attached

1

Connecting pipe 

×

 1 (Connecting pipe is fixed with the unit.)

2

Packing (inside ø23 [29/32 in], outside ø35 [1-13/32 in]) 

×

 1

3

Bushing 

×

 2

7. Water pipe installation

City Multi WY Series pipes are similar to other air-conditioning pipes, however,
please observe the following precautions during installation.

7.1. Precautions during installation

Use the reverse-return method to insure proper pipe resistance to each unit.

To insure easy maintenance, inspection, and replacement of the unit, use a
proper joint, valve, etc. on the water intake and outlet port. In addition, be sure
to install a strainer on the water intake pipe. (In order to maintain the heat
source unit, a strainer on the circulating water inlet is necessary.)
* An example of the heat source unit installation is shown in the diagram be-

low.

Install a suitable air vent on the water pipe. After sending water through the
pipe, be sure to vent the excess air.

Compressed water may form in the low-temperature sections of heat source
unit. Use a drainage pipe connected to the drain valve at the base of the unit to
drain the water.

There is a water vent plug in the center of the heat exchanger water inlet head
at the middle of the unit. Use this for maintenance, etc.
In addition, do not allow any of the unit’s electrical parts (such as the solenoid
valve coil or compressor power supply) to become wet.

Install a back flow-prevention valve on the pump and a flexible joint to prevent
excess vibration.

Use a sleeve to protect the pipes where they go through a wall.

Use metal fittings to secure the pipes, and install them so that they have maxi-
mum protection against breakage and bending.

Do not confuse the water intake and outlet valves.

This unit doesn’t have any heater to prevent freezing within tubes. When the
water flow is stopped on low ambient, take out the water from tubes.

The unused knockout holes should be closed and the opening of refrigerant
pipes, water pipes, power source and transmission wires should be filled with
putty and so on to prevent from rain. (field construction)

Example of heat source unit installation (using left piping)

[Fig. 7.1.1] (P.2)

A

Water circulation pipe

B

Close valve

C

Close valve

D

Water outlet

E

Refrigerant piping

F

Y-type strainer

G

Water inlet

H

Drain pipe

7.2. Insulation installation

With City Multi WY Series piping, as long as the temperature range of the circulat-
ing water is kept to average temperatures year-round (30 

°

C [86 

°

F] in the summer,

20 

°

C [68 

°

F] in the winter), there is no need to insulate or otherwise protect indoor

piping from exposure. You should use insulation in the following situations:

Any heat source piping.

Indoor piping in cold-weather regions where frozen pipes are a problem.

When air coming from the outside causes condensation to form on piping.

Any drainage piping.

7.3. Water processing and water quality con-

trol

To preserve water quality, use the closed type of cooling tower for WY. When the
circulating water quality is poor, the water heat exchanger can develop scales,
leading to a reduction in heat-exchange power and possible corrosion of the heat
exchanger. Please pay careful attention to water processing and water quality control
when installing the water circulation system.

Removal of foreign objects or impurities within the pipes.
During installation, be careful that foreign objects, such as welding fragments,
sealant particles, or rust, do not enter the pipes.

Water Quality Processing

1

Depending on the quality of the cold-temperature water used in the air-
conditioner, the copper piping of the heat exchanger may become corroded.
We recommend regular water quality processing.
Cold water circulation systems using open heat storage tanks are
particularly prone to corrosion.
When using an open-type heat storage tank, install a water-to-water heat
exchanger, and use a closed-loop circuit on the air conditioner side. If a
water supply tank is installed, keep contact with air to a minimum, and
keep the level of dissolved oxygen in the water no higher than 1mg/

r

.

Summary of Contents for CITY MULTI PQHY-P72TGMU-A

Page 1: ...r safe and correct use please read this installation manual thoroughly before installing the air conditioner unit MANUEL D INSTALLATION Veuillez lire le manuel d installation en entier avant d installer ce climatiseur pour éviter tout accident et vous assurer d une utilisation correcte For use with R410A ...

Page 2: ...4 ø14 9 16 Anchoring hole C Top view A Piping space for side piping B Heat source unit C Service space front side D Top view D Anti vibration pad etc E Concrete base E Piping space for top piping F Piping space for side piping G Heat source unit H Front view A Water circulation pipe B Close valve C Close valve D Water outlet A Short circuit wire Connected before delivery from manufacturer B Pump i...

Page 3: ...2 ø15 88 5 8 ø19 05 3 4 ø22 2 7 8 Ó 4 Branching header Downstream unit model total 200 CMY Y104 G 8 Branching header Downstream unit model total 400 CMY Y108 G Ô 10 Branching header Downstream unit model total 650 CMY Y1010 G Ï Downstream unit model total 72 73 400 Ì Branch kit model CMY Y102S G CMY Y102L G Fig 9 2 2 9 2 9 Fig 9 2 1 A B 1 3 A Ball valve Low press side flanged type B Ball valve Hig...

Page 4: ... material C Lagging D Caulking material E Band F Waterproofing laye G Sleeve with edge H Lagging material I Mortar or other incombustible caulking J Incombustible heat insulation material A Power source B Transmission line C Ground screw D C C B B E F G H I J A LO HI LO HI B A K J L H M C D E N O F G I Fig 9 3 1 Fig 9 3 3 Fig 9 3 2 9 3 A A Nitrogen gas B To indoor unit C System analyzer D Lo knob ...

Page 5: ... M1M2S TB5 07 IC M1M2S TB5 06 L 2 L1 MA MA MA OC M1M2 M1M2S TB7 TB3 52 OC c 1 c4 S System controller L3 L 6 L4 c 2 A B A B A B A B M1M2 c 2 c 1 c 1 c2 CN40 CN40 c 3 10 3 B A C 208 230 V B A 208 230 V E E D E E Fig 10 3 2 Fig 10 3 1 A Group 1 B Group 3 C Group 5 D Shielded wire E Sub remote controller Address A Change the jumper connec tor from CN41 to CN40 B SW2 1 ON C Keep the jumper connector on...

Page 6: ...to be exceeded hazards due to lack of oxygen in the room could result When moving and reinstalling the air conditioner consult the dealer or an authorized technician If the air conditioner is installed improperly water leakage electric shock or fire may result After completing installation work make sure that refrigerant gas is not leaking If the refrigerant gas leaks and is exposed to a fan heate...

Page 7: ... valve The vacuum pump oil may flow back into the refrigerant cycle and cause the refrigerator oil to deteriorate Do not use the following tools that are used with conventional refriger ants Gauge manifold charge hose gas leak detector reverse flow check valve refrigerant charge base refrigerant recovery equipment If the conventional refrigerant and refrigerator oil are mixed in the R410A the refr...

Page 8: ... excess air Compressed water may form in the low temperature sections of heat source unit Use a drainage pipe connected to the drain valve at the base of the unit to drain the water There is a water vent plug in the center of the heat exchanger water inlet head at the middle of the unit Use this for maintenance etc In addition do not allow any of the unit s electrical parts such as the solenoid va...

Page 9: ...erator oil will dete riorate Never use existing refrigerant piping The large amount of chlorine in conventional refrigerant and refrigerator oil in the existing piping will cause the new refrigerant to deteriorate Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing If dust dirt or water gets into the refrigerant cycle the oil wi...

Page 10: ...orque by torque wrench Copper pipe external dia mm in Tightening torque N m kg cm ø6 35 1 4 14 to 18 140 to 180 ø9 52 3 8 35 to 42 350 to 420 ø12 7 1 2 50 to 57 5 500 to 575 ø15 88 5 8 75 to 80 750 to 800 ø19 05 3 4 100 to 140 1000 to 1400 Tightening angle standard Pipe diameter mm in Tightening angle ø6 35 1 4 ø9 52 3 8 60 to 90 ø12 7 1 2 ø15 88 5 8 30 to 60 ø19 05 3 4 20 to 35 Fig 9 2 3 P 3 flar...

Page 11: ...ic refriger ant R410A gas leakage causes the composition to change and affects perform ance Therefore perform the airtightness test cautiously Caution Only use refrigerant R410A The use of other refrigerant such as R22 or R407C which contains chlorine will deteriorate the refrigerating machine oil or cause the compressor to malfunction 2 Evacuation Evacuate with the ball valve of the heat source u...

Page 12: ...heat source units whose power supply connector CN41 has been replaced by CN40 the shield terminal S of terminal block TB7 of the central control system should also be connected to the ground screw Fix the wiring securely in place with the cable strap at the bottom of the termi nal block so that the external force if not applied to the terminal block External force applied to the terminal block may...

Page 13: ...A Change the jumper connector from CN41 to CN40 B SW2 1 ON C Keep the jumper connector on CN41 A Group 1 B Group 4 C Group 5 D Shielded wire E Sub remote controller Address Wiring Method and Address Settings a Always use shielded wire when making connections between the heat source unit OC and the indoor unit IC as well for all OC OC and IC IC wiring intervals b Use feed wiring to connect terminal...

Page 14: ...light rain water etc when proceeding with the wiring and connections 3 The wire size is the minimum value for metal conduit wiring The power cord size should be 1 rank thicker consideration of voltage drops Make sure the power supply voltage does not drop more than 10 4 Specific wiring requirements should adhere to the wiring regulations of the region 5 Power supply cords of parts of appliances fo...

Page 15: ...rent utilisez le réfrigérant R410A spécifié sur l appareil Lorsqu un réfrigérant différent est mélangé au réfrigérant d origine il se peut que le cycle du réfrigérant ne fonctionne pas correctement et que l appareil soit endommagé Si le climatiseur est installé dans une pièce relativement petite certaines mesures doivent être prises pour éviter que la concentration de réfrigé rant ne dépasse le se...

Page 16: ...nterventions techniques Si l appareil est raccordé au secteur sans fonctionner le chauffage du carter est toujours sous tension au niveau du compresseur 1 2 Précautions à prendre avec les dispo sitifs utilisant le réfrigérant R410A Précaution N utilisez pas les tuyaux de réfrigérant actuels Le vieux réfrigérant et l huile réfrigérante se trouvant dans les tuyaux con tiennent une large quantité de ...

Page 17: ...e il est conseillé de monter une base anti vibrations sur le socle de support de l appareil Fig 6 1 2 P 2 D Coussinet anti vibrations etc E Socle en béton Avertissement Installez toujours l appareil dans un endroit pouvant supporter son poids Dans le cas contraire l appareil pourrait tomber et par conséquent bles ser quelqu un Effectuez les travaux nécessaires afin d assurer a protection de l appa...

Page 18: ...iez que le niveau d oxygène dissous de l eau ne dépasse pas 1 mg r 2 Norme de qualité de l eau Référence Guideline of Water Quality for Refrigeration and Air Conditioning Equipment Directive relative à la qualité de l eau pour le matériel de réfrigération et de climatisation JRA GL02E 1994 3 Contacter un spécialiste du contrôle de la qualité des eaux pour en savoir plus sur les méthodes de contrôl...

Page 19: ...els Jauge collectrice tuyau flexible de remplissage détecteur de fuites de gaz valve de contrôle base de remplissage de réfrigérant jauge à vide équipements de récupération de réfrigérant Il se peut que l huile réfrigérante se détériore à la suite du mélange d un réfrigérant traditionnel à l huile réfrigérante Il se peut que l huile se détériore si de l eau y est mélangée Le réfrigérant R410A ne c...

Page 20: ...9 1 13 2 16 6 19 7 24 0 dimension de l évasement mm taille de l écrou évasé mm diamètre extérieur ø6 35 ø9 52 ø12 70 ø15 88 ø19 05 taille en pouces 1 4 3 8 1 2 5 8 3 4 dimension B R410A 17 0 22 0 26 0 29 0 36 0 Fig 9 2 2 P 3 A Soupape à bille Côté gaz raccordement à brides B Soupape à bille Côté liquide raccordement évasé C Cette figure montre la soupape complètement ouverte A Tige de la valve Ent...

Page 21: ...istor ROBINAIR 14830A Utiliser également une jauge à vide pouvant atteindre 65 Pa abs 0 00943 psi 0 5 Torr maximum après cinq minutes d utilisation 3 Ajout du réfrigérant Etant donné que le réfrigérant utilisé dans cet appareil est nonazéotropique il doit être dans un état liquide lorsqu ajouté Par conséquent lorsque vous char gez l appareil de réfrigérant à l aide d un cylindre si celui ci n est ...

Page 22: ...ls source de chaleur ou le câblage avec le système de contrôle centralisé au bloc de terminaux de le contrôle centralisé TB7 Lors de l utilisation de câblage blindé raccordez la terre blindée de la ligne de transmission de l appareil intérieur à la vis de terre et raccordez la terre blindée de la ligne située entre les appareils source de chaleur et la ligne de transmission du système de contrôle ...

Page 23: ... M2 et à la borne S des câbles de transmission du bloc de l appareil intérieur IC c Raccorder les bornes 1 M1 et 2 M2 du bloc terminal des câbles de transmission de l appareil intérieur IC qui possède l adresse la plus récente au sein d un même groupe au bloc terminal de la commande à distance RC d Raccordez les bornes M1 M2 et la borne S du bloc de terminaux pour le contrôle centralisé TB7 sur l ...

Page 24: ...jusqu à ce que la température des tuyaux atteigne 35 C 95 F il fonctionne lentement pendant les 2 minutes qui suivent puis il fonctionne selon le préréglage Commande de réglage de la chaleur Le système est en train d être mis en marche Utilisez de nouveau la télécommande lorsque HO ou PLEASE WAIT a dis paru de l affichage Lorsque l appareil s arrête après le mode de refroidissement il continue de ...

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ...HIYODA KU TOKYO 100 8310 JAPAN Please be sure to put the contact address telephone number on this manual before handing it to the customer This product is designed and intended for use in the residential commer cial and light industrial environment Printed in Japan ...

Reviews: