GB

3.1. Securing installation and service space

[Fig. 3.1.1] (P.2)

Select a blowout direction suited for room shape, installation site and so on.

Piping, wiring and maintenance are all done on the bottom and the side. So,
secure the space given above for such work. Also, taking into consideration
serviceability and safety in hanging, secure as large space as possible.

(mm) [in]

3.2. Split flow duct end connection - fresh

air intake

[Fig. 3.2.1] (P.2)

Knockouts are provided at each position as shown in the figure. Use them for
your purposes when installing the unit.

Split flow duct end connection

Split flow duct end connection (435 × 110 knock out on both sides)

6 [1/4] - 

φ 

2.9 [1/8] mounting hole

Note:

Affixed on the back surface of each split flow duct end connection is
insulating material. Use a cutter knife to cut the insulating material
along the end connection.

3.3. Outdoor air inlet

[Fig. 3.3.1] (P.2)

Fresh air intake 

Fresh air intake 

240 [9-15/32] × 45 [1-25/32] knock out hole

4 [3/16] - 

φ

 

2.9 [1/8] mounting hole

Cut

Notes:

A

Make 4 cuts on the outdoor air inlet. When connecting a round flexible
duct, mount an optional outdoor air intake duct flange PAC-KH 11OF
(

φ

150).

B

The amount of suction air coming through the outdoor air inlet can be
adjusted by making two cuts on the outdoor air inlet as shown in the
figure above.

3.4. Combining indoor units with outdoor

units

For combining indoor units with outdoor units, refer to the outdoor unit installation
manual.

4. Fixing hanging bolts

4.1. Fixing hanging bolts

(Give site of suspension strong structure.)

Hanging structure

Ceiling: The ceiling structure varies from building to one another. For detailed
information, consult your construction company.

If necessary, reinforce the hanging bolts with anti-quake supporting members
as countermeasures against earthquakes.

* Use M10 for hanging bolts and anti-quake supporting members (field sup-
ply).

A

Reinforcing the ceiling with additional members (edge beam, etc.) must be
required to keep the ceiling at level and to prevent the ceiling from vibrations.

B

Cut and remove the ceiling members.

C

Reinforce the ceiling members, and add other members for fixing the ceiling
boards.

[Fig. 4.1.1] (P.2)

Center of gravity

Center of gravity and Product  

W

eight

(mm) [in]

(kg) [lb]

4.2. Ceiling hole and hanging bolt positions

Use the gauge supplied with the panel to fix hanging bolts so that the unit
body and ceiling hole are positioned in place as shown in the figure below.
For how to use the gauge, refer to the instruction manual supplied with the
panel.

Notes: 

The gauge may expand or shrink with changes in the temperature and
humidity. First be sure to check the product dimensions, and then use
the gauge.

The ceiling hole is adjustable as shown in the figure below. Align the
centers of both ceiling hole and unit body so that the unit body is not
biased to the ceiling hole and that the gaps between the ceiling hole
edges and the unit body’s external dimensions come to be identical.

Use M10 hanging bolts (for all bolts). (field supply)

Each hanging bolt must extrude Cmm from the ceiling. It is possible to slide
the unit body 10 mm [13/32 in] max. within part of the heights of the unit body
and decorative panel in  order to make fine installation adjustments to the fin-
ished ceiling surface. Sliding the unit body and incorporating a high-perfor-
mance filter requires the dimensions given in the figure below. To this, attach
nuts which will fix a hanging bracket as shown in the figure.

[Fig. 4.2.1] (P.3)

Nut

W

asher (supplied with the unit body)

Hanging bolt 

φ

10 (M10 screw)

Ceiling hole dimensions

Hanging bolt pitch

Hanging bolt

Finished ceiling surface

Hanging bracket

5. Installing the unit

5.1. Hanging the unit body

‹

Bring the indoor unit to an installation site as it is packed.

‹

To hang the indoor unit, use a lifting machine to lift and pass through
the hanging bolts.

‹

When lifting with a lifting machine, in order to protect against damage,
reverse the unit body as is packed with the packing cap and lift it.

[Fig. 5.1.1] (P.3)

Drain pipe side

Unit body

Packing cap

Lifting machine

Model name

06-15

18

A

1080 [42-17/32]

1250 [49-7/32]

B

More than 1000 [39-3/8]

C

More than 500 [19-11/16]

D

Lap: 20 [13/16]

E

More than 350 [13-25/32]

Model 

name

W

L

H

X

Y

Z

Unit 

W

eight

Panel 

W

eight

PLFY-P06 

NLMU-E

574

[22-5/8]

824

[32-15/32]

172

[6-25/32]

287

[11-5/16]

370

[14-19/32]

160

[6-5/16]

23

[51]

6.5

[15]

PLFY-P08 

NLMU-E

574

[22-5/8]

824

[32-15/32]

172

[6-25/32]

287

[11-5/16]

370

[14-19/32]

160

[6-5/16]

23

[51]

6.5

[15]

PLFY-P12 

NLMU-E

574

[22-5/8]

824

[32-15/32]

172

[6-25/32]

287

[11-5/16]

370

[14-19/32]

160

[6-5/16]

24

[53]

6.5

[15]

PLFY-P15 

NLMU-E

574

[22-5/8]

824

[32-15/32]

172

[6-25/32]

287

[11-5/16]

370

[14-19/32]

160

[6-5/16]

24

[53]

6.5

[15]

PLFY-P18 

NLMU-E

574

[22-5/8]

994

[32-5/32]

172

[6-25/32]

287

[11-5/16]

445

[17-17/32]

160

[6-5/16]

27

[60]

7.5

[17]

Model name

06 – 15

18

A

1040 [40-31/32]

1210 [47-21/32]

B

824 [32-15/32]

994 [39-5/32]

C

157 – 167 [6-3/16~6-19/32]

D

More than 350 [13-25/32]

Summary of Contents for City Multi PLFY-P-NLMU-E

Page 1: ...UAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit MANUEL D INSTALLATION Veuillez lire manuel d installation en entier avant d installer ce climatiseur pour éviter tout accident et vous assurrer d une utilisation correcte ...

Page 2: ...2 mm in Model name 06 15 18 A 1080 42 17 32 1250 49 7 32 B More than 1000 39 3 8 C More than 500 19 11 16 D Lap 20 13 16 E More than 350 13 25 32 110 4 11 32 159 6 9 32 52 2 1 16 34 1 11 32 435 17 5 32 06 15 218 8 19 32 218 8 19 32 221 8 23 32 110 4 11 32 52 2 1 16 159 6 9 32 34 1 11 32 435 17 5 32 218 8 19 32 218 8 19 32 221 8 23 32 18 216 8 1 2 45 197 7 25 32 240 9 15 32 A A A 1 25 32 Fresh air ...

Page 3: ... 1 1 Drain pipe side Unit body Packing cap Lifting machine Fig 5 2 1 Indoor unit s bottom surface Surface to which a decorative panel is attached 6 6 1 6 2 Fig 6 1 1 Flare cutting dimensions Refrigerant pipe sizes Flare nut tightening torque Apply refrigerating machine oil over the entire flare seat surface Fig 6 2 1 Refrigerant pipe liquid pipe Drain pipe Hanging bolt pitch Refrigerant pipe gas p...

Page 4: ... cm 9 27 32 in B 1 5 2 m 4 7 8 6 1 2 ft Downward slope of more than 1 100 Insulating material Metal brace Fig 7 2 2 Indoor unit Take as large as possible About 10 cm 3 15 16 in Collected pipes Fig 7 3 1 Fig 7 2 3 C 28 cm 11 1 32 in D 170 5 mm 6 23 32 7 32 in Drain hose Accessory Be sure to use the supplied drain hose Accessory Less than 300 mm 11 13 16 in Hard vinyl chloride 90 elbow field supply ...

Page 5: ...larized 2 wire 8 3 Fig 8 3 1 Side frame Cover Screw 2 places Fig 8 3 2 Viewed from bottom of the terminal bed box Terminal bed for transmission cable Transmission cable To terminal bed for M NET remote controller indoor unit and BC controller To single phase power supply Terminal bed for power supply To terminal bed for M NET outdoor transmission cable 8 4 Fig 8 4 1 Address switch TB5 TB15 TB5 TB1...

Page 6: ...ations and the instructions given in this manual and always use a special circuit If the power source capacity is inadequate or electric work is performed improperly electric shock and fire may result Securely install the outdoor unit terminal cover panel If the terminal cover panel is not installed properly dust or water may enter the outdoor unit and fire or electric shock may result When instal...

Page 7: ... fall and cause personal injury or property damage Install the drain piping according to this Installation Manual to ensure proper drainage Wrap thermal insulation around the pipes to prevent condensation Improper drain piping may cause water leakage and damage to furniture and other possessions Be very careful about product transportation Only one person should not carry the product if it weighs ...

Page 8: ...ts so that the unit body and ceiling hole are positioned in place as shown in the figure below For how to use the gauge refer to the instruction manual supplied with the panel Notes The gauge may expand or shrink with changes in the temperature and humidity First be sure to check the product dimensions and then use the gauge The ceiling hole is adjustable as shown in the figure below Align the cen...

Page 9: ...g connection Description of parts to be used Pipe size Insulating material s thickness 6 4 mm to 25 4 mm 1 4 in to 1 in More than 10 mm 13 32 in 28 6 mm to 38 1 mm 1 1 8 in to 1 1 2 in More than 15 mm 19 32 in Copper pipe O D mm in Flare dimensions φ A dimensions mm in φ 6 35 1 4 8 7 9 1 11 32 6 16 φ 9 52 3 8 12 8 13 2 17 32 17 32 φ 12 7 1 2 16 2 16 6 21 32 21 32 φ 15 88 5 8 19 3 19 7 25 32 25 32 ...

Page 10: ... the piping sealed until just before brazing If dust dirt or water gets into the refrigerant cycle the oil will deteriorate and the compressor may fail Use Suniso 4GS or 3GS small amount refrigerator oil to coat the flare and flange connection part For models using R22 Use ester oil ether oil or alkylbenzene small amount as the refrigerator oil to coat flares and flange connections For models usin...

Page 11: ...er and the outdoor unit 8 Select control cables from the conditions given in below Caution Be sure to ground the indoor unit Do not connect the grounding cable to any gas pipe water pipe lightening rod or telephone earth cable Incom plete grounding may cause a risk of electric shock Types of control cables 1 Wiring transmission cables Types of transmission cables Shielding wire CVVS or CPEVS Cable...

Page 12: ...o within 200 m 656 ft 3 The BC controller is required only for simultaneous cooling and heating series R2 8 3 Connecting electrical connections Be sure to prevent terminal screws from loosening 1 Remove 2 screws which secures the terminal bed box cover using a screw driver A Fig 8 3 1 P 5 Side frame Cover Screw 2 places 2 As shown at B wire the power supply transmission cable and remote con trolle...

Page 13: ...lectrocution ou un incendie Ne jamais réparer l appareil soi même Dans le cas où l appareil doit être réparé s adresser au revendeur Si l appareil est réparé incorrectement cela peut entraîner une fuite d eau une électrocution ou un incendie Ne pas toucher aux ailettes de l échangeur de chaleur Une manipulation incorrecte peut entraîner des blessures Toujours porter des vêtements de protection lor...

Page 14: ...e communications ou tout autre endroit similaire veiller à fournir une protection suffisante contre le bruit Les équipements inverseurs les générateurs privés les équipements médi caux à haute fréquence ou les équipements de communication radio peu vent empêcher le climatiseur de fonctionner correctement ou de fonctionner De plus le climatiseur peut affecter le fonctionnement de ces équipements et...

Page 15: ...er le plus d espace possible mm in 3 2 Raccordement de l extrémité de la gaine d écoulement divisé Prise d air frais Fig 3 2 1 P 2 Des séparateurs sont fournis pour chaque emplacement comme montré dans la figure Les utiliser comme nécessaire lors de l installation de l appar eil Raccordement de l extrémité de la gaine d écoulement divisé Raccordement de l extrémité de la gaine d écoulement divisé ...

Page 16: ...lons de suspension sont bien positionnés en place S ils ne sont pas bien positionnés en place cela peut entraîner l égouttement de la condensation à la suite d une fuite d air Veiller à bien vérifier les positions relatives Utiliser un niveau d eau pour vérifier l horizontalité de la surface S assurer que les écrous des boulons de suspension sont bien serrés pour fixer les boulons de suspension Po...

Page 17: ...r machine réfrigérante et resserrer le raccordement à l aide d une clé double Fournir une entretoise en métal pour supporter le tuyau de réfrigérant de façon à appliquer la charge au tuyau d extrémité de l appareil intérieur Cette entretoise en métal doit être placée à 50 cm 19 11 16 in du raccordement de l évasement de l appareil intérieur Diamètre extérieur du tuyau en cuivre mm in Dimensions de...

Page 18: ...tacles au dessous du plafond utiliser des coudes pour la mettre au moins aussi haut que le site C Remarque Si la partie montante est longue une grande quantité d eau reflue lors de l arrêt du fonctionnement générant de la boue ou une odeur pendant la sai son creuse S assurer que la partie montante est gardée à un minimum Précaution S assurer du déchargement de la tuyauterie d écoulement et l isole...

Page 19: ...s tendus peuvent se rompre ou surchauffer et brûler Fixer les câbles de la source d alimentation au boîtier de commande à l aide d un manchon butoir pour la force de tension Raccordement PG ou simi laire Raccorder les câbles de transmission au bloc de sortie de transmis sion par le biais de l orifice à détacher du boîtier de commande à l aide d un manchon ordinaire Après avoir effectué le câblage ...

Page 20: ... volonté l adresse des appareils et le numéro des branchements La détermination des adresses intérieures varie en fonction du système sur place Les configurer en se reportant aux données techniques Remarques Prière de régler l interrupteur SW5 en fonction de la tension d alimentation 8 5 Détection de la température de la pièce à l aide du capteur incorporé dans la commande à distance Pour détecter...

Page 21: ...M E M O ...

Page 22: ...M E M O ...

Page 23: ...OKYO 100 8310 JAPAN This product is designed and intended for use in the residential commer cial and light industrial environment Please be sure to put the contact address telephone number on this manual before handing it to the customer Printed in Japan WT04567X01 ...

Reviews: