Contents

1. Safety precautions ........................................................................................ 6

1.1. Before installation and electric work ............................................ 6
1.2. Precautions for devices that use R410A or R22 refrigerant ........ 6
1.3. Before getting installed ................................................................ 7
1.4. Before getting installed (moved) - electrical work ........................ 7
1.5. Before starting the test run .......................................................... 7

2. Indoor unit accessories ................................................................................. 7
3. Selecting an installation site.......................................................................... 7

3.1. Securing installation and service space ...................................... 8
3.2. Split flow duct end connection - fresh air intake .......................... 8
3.3. Outdoor air inlet ........................................................................... 8
3.4. Combining indoor units with outdoor units................................... 8

4. Fixing hanging bolts ...................................................................................... 8

4.1. Fixing hanging bolts..................................................................... 8
4.2. Ceiling hole and hanging bolt positions ....................................... 8

5. Installing the unit ........................................................................................... 8

5.1. Hanging the unit body.................................................................. 8

5.2. Confirming the unit’s position and fixing hanging bolts ................9

6. Refrigerant pipe and drain pipe specifications .............................................. 9

6.1. Refrigerant pipe and drain pipe specifications .............................9
6.2. Refrigerant pipe , drain pipe and filling port ................................. 9
6.3. Request for refrigerant piping connection ....................................9

7. Connecting refrigerant pipes and drain pipes..............................................10

7.1. Refrigerant piping work..............................................................10
7.2. Drain piping work .......................................................................10
7.3. Confirming drain discharge........................................................10

8. Electrical wiring ...........................................................................................11

8.1. Power supply wiring ...................................................................11
8.2. Connecting remote controller, indoor and outdoor transmission 

cables ........................................................................................12

8.3. Connecting electrical connections .............................................12
8.4. Setting addresses ......................................................................12
8.5. Sensing room temperature with the built-in sensor in a remote 

controller ....................................................................................12

1. Safety precautions

1.1. Before installation and electric work

Symbols used in the text

 Warning:

Describes precautions that should be observed to prevent danger of injury
or death to the user.

 Caution:

Describes precautions that should be observed to prevent damage to the
unit.

Symbols put on the unit

 Warning:

• Ask the dealer or an authorized technician to install the air conditioner.

- Improper installation by the user may result in water leakage, electric shock,

or fire.

• Install the air unit at a place that can withstand its weight.

- Inadequate strength may cause the unit to fall down, resulting in injuries.

• Use the specified cables for wiring. Make the connections securely so

that the outside force of the cable is not applied to the terminals.

- Inadequate connection and fastening may generate heat and cause a fire.

• Prepare for typhoons and other strong winds and earthquakes and

install the unit at the specified place.

- Improper installation may cause the unit to topple and result in injury.

• Always use an air cleaner, humidifier, electric heater, and other accesso-

ries specified by Mitsubishi Electric.

- Ask an authorized technician to install the accessories. Improper installation

by the user may result in water leakage, electric shock, or fire.

• Never repair the unit. If the air conditioner must be repaired, consult the

dealer.

- If the unit is repaired improperly, water leakage, electric shock, or fire may

result.

• Do not touch the heat exchanger fins.

- Improper handling may result in injury.

• When handling this product, always wear protective equipment.

EG: Gloves, full arm protection namely boiler suit, and safety glasses.

- Improper handling may result in injury.

• If refrigerant gas leaks during installation work, ventilate the room.

- If the refrigerant gas comes into contact with a flame, poisonous gases will

be released.

• Install the air conditioner according to this Installation Manual.

- If the unit is installed improperly, water leakage, electric shock, or fire may

result.

• Have all electric work done by a licensed electrician according to “Elec-

tric Facility Engineering Standard” and “Interior Wire Regulations”and
the instructions given in this manual and always use a special circuit.

- If the power source capacity is inadequate or electric work is performed

improperly, electric shock and fire may result.

• Securely install the outdoor unit terminal cover (panel).

- If the terminal cover (panel) is not installed properly, dust or water may enter

the outdoor unit and fire or electric shock may result.

• When installing and moving the air conditioner to another site, do not

charge the it with a refrigerant different from the refrigerant specified on
the unit.

- If a different refrigerant or air is mixed with the original refrigerant, the refrig-

erant cycle may malfunction and the unit may be damaged.

• If the air conditioner is installed in a small room, measures must be taken

to prevent the refrigerant concentration from exceeding the safety limit
even if the refrigerant should leak.

- Consult the dealer regarding the appropriate measures to prevent the safety

limit from being exceeded. Should the refrigerant leak and cause the safety
limit to be exceeded, hazards due to lack of oxygen in the room could result.

• When moving and reinstalling the air conditioner, consult the dealer or

an authorized technician.

- If the air conditioner is installed improperly, water leakage, electric shock, or

fire may result.

• After completing installation work, make sure that refrigerant gas is not

leaking.

- If the refrigerant gas leaks and is exposed to a fan heater, stove, oven, or

other heat source, it may generate noxious gases.

• Do not reconstruct or change the settings of the protection devices.

- If the pressure switch, thermal switch, or other protection device is shorted

and operated forcibly, or parts other than those specified by Mitsubishi Elec-
tric are used, fire or explosion may result.

• To dispose of this product, consult your dealer.
• Do not use a leak detection additive.

1.2. Precautions for devices that use R410A

or R22 refrigerant

 Caution:

• Do not use the existing refrigerant piping.

- The old refrigerant and refrigerator oil in the existing piping contains a large

amount of chlorine which may cause the refrigerator oil of the new unit to
deteriorate.

• Use refrigerant piping made of C1220 (Cu-DHP) phosphorus deoxidized

copper as specified in the JIS H3300 “Copper and copper alloy seamless
pipes and tubes”. In addition, be sure that the inner and outer surfaces
of the pipes are clean and free of hazardous sulphur, oxides, dust/dirt,
shaving particles, oils, moisture, or any other contaminant.

- Contaminants on the inside of the refrigerant piping may cause the refriger-

ant residual oil to deteriorate.

• Store the piping to be used during installation indoors and keep both

ends of the piping sealed until just before brazing. (Store elbows and
other joints in a plastic bag.)

- If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and

compressor trouble may result.

• Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerator

oil to coat flares and flange connections.

- The refrigerator oil will degrade if it is mixed with a large amount of mineral

oil.

‹

Before installing the unit, make sure you read all the “Safety
precautions”.

‹

The “Safety precautions” provide very important points
regarding safety. Make sure you follow them.

: Indicates an action that must be avoided.

: Indicates that important instructions must be followed.

: Indicates a part which must be grounded.

: Indicates that caution should be taken with rotating parts. (This symbol

is displayed on the main unit label.) <Color: yellow>

: Beware of electric shock (This symbol is displayed on the main unit

label.) <Color: yellow>

 Warning:

Carefully read the labels affixed to the main unit.

Summary of Contents for City Multi PLFY-P-NLMU-E

Page 1: ...UAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit MANUEL D INSTALLATION Veuillez lire manuel d installation en entier avant d installer ce climatiseur pour éviter tout accident et vous assurrer d une utilisation correcte ...

Page 2: ...2 mm in Model name 06 15 18 A 1080 42 17 32 1250 49 7 32 B More than 1000 39 3 8 C More than 500 19 11 16 D Lap 20 13 16 E More than 350 13 25 32 110 4 11 32 159 6 9 32 52 2 1 16 34 1 11 32 435 17 5 32 06 15 218 8 19 32 218 8 19 32 221 8 23 32 110 4 11 32 52 2 1 16 159 6 9 32 34 1 11 32 435 17 5 32 218 8 19 32 218 8 19 32 221 8 23 32 18 216 8 1 2 45 197 7 25 32 240 9 15 32 A A A 1 25 32 Fresh air ...

Page 3: ... 1 1 Drain pipe side Unit body Packing cap Lifting machine Fig 5 2 1 Indoor unit s bottom surface Surface to which a decorative panel is attached 6 6 1 6 2 Fig 6 1 1 Flare cutting dimensions Refrigerant pipe sizes Flare nut tightening torque Apply refrigerating machine oil over the entire flare seat surface Fig 6 2 1 Refrigerant pipe liquid pipe Drain pipe Hanging bolt pitch Refrigerant pipe gas p...

Page 4: ... cm 9 27 32 in B 1 5 2 m 4 7 8 6 1 2 ft Downward slope of more than 1 100 Insulating material Metal brace Fig 7 2 2 Indoor unit Take as large as possible About 10 cm 3 15 16 in Collected pipes Fig 7 3 1 Fig 7 2 3 C 28 cm 11 1 32 in D 170 5 mm 6 23 32 7 32 in Drain hose Accessory Be sure to use the supplied drain hose Accessory Less than 300 mm 11 13 16 in Hard vinyl chloride 90 elbow field supply ...

Page 5: ...larized 2 wire 8 3 Fig 8 3 1 Side frame Cover Screw 2 places Fig 8 3 2 Viewed from bottom of the terminal bed box Terminal bed for transmission cable Transmission cable To terminal bed for M NET remote controller indoor unit and BC controller To single phase power supply Terminal bed for power supply To terminal bed for M NET outdoor transmission cable 8 4 Fig 8 4 1 Address switch TB5 TB15 TB5 TB1...

Page 6: ...ations and the instructions given in this manual and always use a special circuit If the power source capacity is inadequate or electric work is performed improperly electric shock and fire may result Securely install the outdoor unit terminal cover panel If the terminal cover panel is not installed properly dust or water may enter the outdoor unit and fire or electric shock may result When instal...

Page 7: ... fall and cause personal injury or property damage Install the drain piping according to this Installation Manual to ensure proper drainage Wrap thermal insulation around the pipes to prevent condensation Improper drain piping may cause water leakage and damage to furniture and other possessions Be very careful about product transportation Only one person should not carry the product if it weighs ...

Page 8: ...ts so that the unit body and ceiling hole are positioned in place as shown in the figure below For how to use the gauge refer to the instruction manual supplied with the panel Notes The gauge may expand or shrink with changes in the temperature and humidity First be sure to check the product dimensions and then use the gauge The ceiling hole is adjustable as shown in the figure below Align the cen...

Page 9: ...g connection Description of parts to be used Pipe size Insulating material s thickness 6 4 mm to 25 4 mm 1 4 in to 1 in More than 10 mm 13 32 in 28 6 mm to 38 1 mm 1 1 8 in to 1 1 2 in More than 15 mm 19 32 in Copper pipe O D mm in Flare dimensions φ A dimensions mm in φ 6 35 1 4 8 7 9 1 11 32 6 16 φ 9 52 3 8 12 8 13 2 17 32 17 32 φ 12 7 1 2 16 2 16 6 21 32 21 32 φ 15 88 5 8 19 3 19 7 25 32 25 32 ...

Page 10: ... the piping sealed until just before brazing If dust dirt or water gets into the refrigerant cycle the oil will deteriorate and the compressor may fail Use Suniso 4GS or 3GS small amount refrigerator oil to coat the flare and flange connection part For models using R22 Use ester oil ether oil or alkylbenzene small amount as the refrigerator oil to coat flares and flange connections For models usin...

Page 11: ...er and the outdoor unit 8 Select control cables from the conditions given in below Caution Be sure to ground the indoor unit Do not connect the grounding cable to any gas pipe water pipe lightening rod or telephone earth cable Incom plete grounding may cause a risk of electric shock Types of control cables 1 Wiring transmission cables Types of transmission cables Shielding wire CVVS or CPEVS Cable...

Page 12: ...o within 200 m 656 ft 3 The BC controller is required only for simultaneous cooling and heating series R2 8 3 Connecting electrical connections Be sure to prevent terminal screws from loosening 1 Remove 2 screws which secures the terminal bed box cover using a screw driver A Fig 8 3 1 P 5 Side frame Cover Screw 2 places 2 As shown at B wire the power supply transmission cable and remote con trolle...

Page 13: ...lectrocution ou un incendie Ne jamais réparer l appareil soi même Dans le cas où l appareil doit être réparé s adresser au revendeur Si l appareil est réparé incorrectement cela peut entraîner une fuite d eau une électrocution ou un incendie Ne pas toucher aux ailettes de l échangeur de chaleur Une manipulation incorrecte peut entraîner des blessures Toujours porter des vêtements de protection lor...

Page 14: ...e communications ou tout autre endroit similaire veiller à fournir une protection suffisante contre le bruit Les équipements inverseurs les générateurs privés les équipements médi caux à haute fréquence ou les équipements de communication radio peu vent empêcher le climatiseur de fonctionner correctement ou de fonctionner De plus le climatiseur peut affecter le fonctionnement de ces équipements et...

Page 15: ...er le plus d espace possible mm in 3 2 Raccordement de l extrémité de la gaine d écoulement divisé Prise d air frais Fig 3 2 1 P 2 Des séparateurs sont fournis pour chaque emplacement comme montré dans la figure Les utiliser comme nécessaire lors de l installation de l appar eil Raccordement de l extrémité de la gaine d écoulement divisé Raccordement de l extrémité de la gaine d écoulement divisé ...

Page 16: ...lons de suspension sont bien positionnés en place S ils ne sont pas bien positionnés en place cela peut entraîner l égouttement de la condensation à la suite d une fuite d air Veiller à bien vérifier les positions relatives Utiliser un niveau d eau pour vérifier l horizontalité de la surface S assurer que les écrous des boulons de suspension sont bien serrés pour fixer les boulons de suspension Po...

Page 17: ...r machine réfrigérante et resserrer le raccordement à l aide d une clé double Fournir une entretoise en métal pour supporter le tuyau de réfrigérant de façon à appliquer la charge au tuyau d extrémité de l appareil intérieur Cette entretoise en métal doit être placée à 50 cm 19 11 16 in du raccordement de l évasement de l appareil intérieur Diamètre extérieur du tuyau en cuivre mm in Dimensions de...

Page 18: ...tacles au dessous du plafond utiliser des coudes pour la mettre au moins aussi haut que le site C Remarque Si la partie montante est longue une grande quantité d eau reflue lors de l arrêt du fonctionnement générant de la boue ou une odeur pendant la sai son creuse S assurer que la partie montante est gardée à un minimum Précaution S assurer du déchargement de la tuyauterie d écoulement et l isole...

Page 19: ...s tendus peuvent se rompre ou surchauffer et brûler Fixer les câbles de la source d alimentation au boîtier de commande à l aide d un manchon butoir pour la force de tension Raccordement PG ou simi laire Raccorder les câbles de transmission au bloc de sortie de transmis sion par le biais de l orifice à détacher du boîtier de commande à l aide d un manchon ordinaire Après avoir effectué le câblage ...

Page 20: ... volonté l adresse des appareils et le numéro des branchements La détermination des adresses intérieures varie en fonction du système sur place Les configurer en se reportant aux données techniques Remarques Prière de régler l interrupteur SW5 en fonction de la tension d alimentation 8 5 Détection de la température de la pièce à l aide du capteur incorporé dans la commande à distance Pour détecter...

Page 21: ...M E M O ...

Page 22: ...M E M O ...

Page 23: ...OKYO 100 8310 JAPAN This product is designed and intended for use in the residential commer cial and light industrial environment Please be sure to put the contact address telephone number on this manual before handing it to the customer Printed in Japan WT04567X01 ...

Reviews: