MITSUBISHI ELECTRIC 9900D SERIES UPS
9900D SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
7-6
Table 7.1
Bypass Module Fault Code List
Code
indication
(Note 2)
Status
Message
Meaning
Guidance
Audible
Alarm
External
relay
contact
(Note 1)
UF384
CTRL.CIRCUIT ERR.
Minor communication error by
fall-out of only A-side of dual
connector.
CALL
SERVICE
ENGINEER
Intermittent
sound
Minor
UF385
CTRL.CIRCUIT ERR.
Minor communication error by
fall-out of only B-side of dual
connector.
CALL
SERVICE
ENGINEER
Intermittent
sound
Minor
UF386
LCD FAULT
Communication error with LCD
CALL
SERVICE
ENGINEER
Intermittent
sound
Minor
UF401
52S ABNORMAL
Error to close the contactor 52S.
CALL
SERVICE
ENGINEER
Continuous
sound
Major
UF402
52S ABNORMAL
Error to open the contactor 52S.
CALL
SERVICE
ENGINEER
Continuous
sound
Major
UF420
52L OPERATION
ERR.
Load circuit breaker 52L opened
during inverter operation.
CALL
SERVICE
ENGINEER
Continuous
sound
Major
UF451
52S ABNORMAL
Contactor 52S failed during load
transfer from inverter to bypass.
CALL
SERVICE
ENGINEER
Intermittent
sound
Minor
UF452
CB3 ABNORMAL
Contactor CB3 is not working
properly.
CALL
SERVICE
ENGINEER
Intermittent
sound
Minor
UF453
STS TEMP.
ABNOMAL
Thyristor temperature abnormal
CALL
SERVICE
ENGINEER
Intermittent
sound
Minor