Table 7.2
UPS Module Fault Code List
Code
indication
(Note 2)
Status
message
Meaning
External relay
contact
(Note 1)
MF202
INVERTER UV.
Output voltage dropped.
Major
MF203
INVERTER OC.
Detection of inverter overcurrent.
Major
MF204
O/P CIRCUIT ABNL.
Detection of a large variation of the reference error
signal (current reference and actual current).
Major
MF207
ZERO PHASE OC.
Inverter zero-sequence overcurrent.
Major
MF208
CTRL.CIRCUIT ERR.
Cross current is abnormal.
Major
MF210
52C ABNORMAL
Error to open the contactor 52C.
Major
MF213
OVERTEMPERATURE
Heatsinks temperature exceeds thermal settings.
Major
MF214
COOLING FAN ABNL.
Thermal relay activated protection.
Major
MF217
INVERTER OV.
Detection of inverter output phase overvoltage.
Major
MF230
ZERO PHASE OC.
Detection of zero-sequence overcurrent.
Major
MF253
CTRL.CIRCUIT ERR.
Discrepancy between output voltage and inverter
voltage, or between output voltage and bypass
voltage.
Minor
MF254
COOLING FAN ABNL
Fan Failure (Minor)
Minor
MF256
O/P VOLTAGE ABNL.
Output voltage is out of the specified range.
Minor
MF301
CTRL.CIRCUIT ERR.
AD reference has an abnormal value.
Major
MF302
CTRL.CIRCUIT ERR.
Detection of an external interruption during the
software execution.
Major
MF303
CTRL.CIRCUIT ERR.
Timer does not reset in the specified period (WDT
settings)
Major
MF305
CTRL.CIRCUIT ERR.
Detection of an abnormal clock speed in the DSP or
FPGA.
Major
MF306
CTRL.CIRCUIT ERR.
Control power supply voltage is below the specified
level.
Major
MF309
INV.VOLTAGE ABNL.
Inverter voltage is out of the specified range.
Major
MF320
CTRL.CIRCUIT ERR.
Cable disconnection in the parallel interface board
during load supply.
Major
MF331
CTRL.CIRCUIT ERR.
Cable disconnection in the main driver PCB (Phase U)
Major
Summary of Contents for 9900D Series