MITSUBISHI ELECTRIC 9900D SERIES UPS
9900D SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
3-15
3.4 CONNECTION OF BATTERY UVR SIGNAL
UVR section only applicable for units without an internal CB2.
1. In the Bypass Cabinet, connect the 2 loose yellow wires to the UVR terminal block. Attach wires
46-1 to terminal #1 and 46-3 to terminal #3 as shown in Figure 3.11. See Figure 3.12 for full wiring
diagram.
Figure 3.11
UVR Terminal
Block
2. Connect the remaining UVR signal wires between power modules as shown in Figure 3.12.
Figure 3.12
Diagram of UVR Connection Between Power Modules
!