MITSUBISHI ELECTRIC 9900D SERIES UPS
9900D SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
7-2
BYPASS MODULE FAULT CODES
Table 7.1
Bypass Module Fault Code List
Code
indication
(Note 2)
Status
Message
Meaning
Guidance
Audible
Alarm
External
relay
contact
(Note 1)
UA805
OVERLOAD
The output load current has
exceeded 100% of the rated
current.
WARNING:
DECREASE
LOAD
Intermittent
sound
Overload
UA806
INVERTER
OVERLOAD
The output load current peak has
exceeded 220% of the rated
current.
WARNING:
DECREASE
LOAD
Intermittent
sound
Overload
UA807
INVERTER
OVERLOAD
The output load current has
exceeded 105%~149% of the
rated current.
WARNING:
DECREASE
LOAD
Intermittent
sound
Overload
UA808
OVERLOAD
The output load current has
exceeded 100% of the rated
current during bypass supply.
WARNING:
DECREASE
LOAD
Intermittent
sound
Overload
UA810
OVERLOAD
Short time over-current has
exceeded 150% of the rated
current.
WARNING:
DECREASE
LOAD
Intermittent
sound
Overload
UA812
BYPS.VOLT.OUT
RNG.
Bypass line voltage is out of the
specific range.
(Detection Level: <87%, >112% )
CHECK
BYPASS
INPUT
Intermittent
sound
Bypass
Input
Abnormal
UA813
BYPS.PHASE ABNL.
Bypass line power conductors
are not wired in a proper phase
sequence.
CHECK
BYPASS
INPUT
Intermittent
sound
Bypass
Input
Abnormal
UA814
BYPS.FREQ.OUT
RNG.
Bypass line frequency is out of
the specific range.
(Detection Level: Frequency
Ban0.2%)
CHECK
BYPASS
INPUT
Intermittent
sound
Bypass
Input
Abnormal
UA815
TRANSFER
PROHIBITION
Transfer to bypass is not
available due to bypass
abnormality.
-
Intermittent
sound
-
UA816
BYP.VOLT.OUT
RNG.2
Bypass line voltage is out of the
specified range at ECO mode.
CALL
SERVICE
ENGINEER
Intermittent
sound
-
UA817
EMERG.STOP ACTIV.
The emergency stop was
activated by the EPO switch or
an external contact.
-
Continuous
sound
-
UA818
MODULE STOP
Input Failure and UPS stop
(Indiv. BAT only)
-
Intermittent
sound
-
UA821
REM. BUTTON
CLOSE
The UPS could not transfer to the
bypass because the inverter
output was not synchronized to
the bypass.
-
Intermittent
sound
-
UA822
LOC. BUTTON ABNL.
The UPS could not transfer to the
bypass because of backup
generator operation.
CALL
SERVICE
ENGINEER
Intermittent
sound
-
UA824
CB2 OPEN
The battery circuit breaker (CB2)
is open.
TURN ON
CB2
Intermittent
sound
-
UA831
EMERG.BYPS.SW.ON Emergency bypass switch has
been turned on.
CALL
SERVICE
ENGINEER
Intermittent
sound
-
UA833
52L OPEN
The load circuit breaker (52L) is
turned off.
-
Intermittent
sound
-
UA834
BATTERY DEPLETED The battery voltage has reached
the depleted level (400V).
CALL
SERVICE
ENGINEER
-
Battery
Depleted
UA835
TRANS.INHIBITED
The UPS could not transfer to the
bypass because the bypass
source has an abnormality.
-
-
-
Summary of Contents for 9900D Series