MITSUBISHI ELECTRIC 9900D SERIES UPS
9900D SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
3-8
Table 3.3
Recommended Cable Sizes
kVA
Capacity
Input
Voltage
Output
Voltage
Input Side
Cable Size
Output Side
Cable Size
Bypass Side
Cable Size
DC Input Side Cable
Size
1200kVA
480V
480V
5 x 500MCM
5 x 500MCM
5 x 500MCM
9 x 500MCM
1250kVA
480V
480V
5 x 500MCM
5 x 500MCM
5 x 500MCM
9 x 500MCM
1500kVA
480V
480V
7 x 500MCM
7 x 500MCM
7 x 500MCM
11 x 500MCM
1600kVA
480V
480V
7 x 500MCM
7 x 500MCM
7 x 500MCM
11 x 500MCM
2000kVA
480V
480V
9 x 500MCM
8 x 500MCM
8 x 500MCM
14 x 500MCM
*1 – Use 75 degree C copper wire.
*2 - The cables shall be selected to be equal or larger to the sizes listed in the table.
*3 - Voltage drop across power cables not to exceed 2% of nominal source voltage.
*4 - Allowable ampere-capacities based on copper conductors with 75 degree C. insulation at ambient temperature of 40 degree C.
Table 3.4
Recommended Hardware
Bolt size
Flat washer
size
Split
lockwasher
size
Nut Size
Grade
Torque
in. lbs
M12 x 40mm
M12
M12
M12
ISO 4.8
347 - 469
in. lbs