16
3.
Use
3.9
Change the duration between automatic spool cycles
The spool function is used to prevent the formation of legionella and other waterborne
pathogenic microorganisms in the water system. The system will automatically spool
itself with water after a certain amount of time the system has not dispensed water
while connected to a power supply. While spooling, the system automatically passes
step by step the entire temperature field beginning with cold water and ending with hot
water.
NOTE
In order for the automatic spool function to work correctly please ensure the following
conditions are met:
•
the miscea system must be always be connected to power
•
the duration of the automatic spool cycle is not set to 0 min.
See 3.10 “Change duration of automatic spool cycle”
Press «SPOOL» button. The water sector will light up. With the «+» and «-» buttons on
the remote control, the duration of time between spool cycles can be changed. To save
settings, press the «SAVE» button. All colored LED lights illuminate to indicate the new
setting has been saved. If the «SAVE» button is not pressed within 10 seconds of the
last selection, the previously saved setting will be stored.
3.10
Change duration of automatic spool cycle
During the spool cycle, water will automatically dispense for a certain amount of time
referred to as the DURATION on the remote control. While spooling, the system auto-
matically passes step by step the entire temperature field beginning with cold water and
ending with hot water.
Press the «DURATION» button. The water sector will light up. With the «+» and «-»
buttons, the duration of continuous water flow in spool mode can be changed. To save
settings, press the «SAVE» button. All colored LED lights illuminate to indicate the new
setting has been saved. If the «SAVE» button is not pressed within 10 seconds of the
last selection, the previously saved setting will be stored.
SPOOL
Position
1
2
3
4
5
6
7
8
9
Bar position
Min
Max
Time between Spool Cycle
in hours
0
4*
24
8*
48
12*
72
24*
96
48*
120
72*
144
96*
168
120*
252
Duration of Spool Cycle
in minutes
0
2
4
6
8
10
15
20
30
CLASSIC
Ä
LIGHT
Ä
KITCHEN
Ä
EN: From faucet software version 1.59 and higher, times marked with * apply.
DURATION