Calibration procedure
Calibrate the drive using the following procedure:
1. Set the MIN SPD, MAX SPD, ACCEL and DECEL trimpots to
zero (full CCW).
2. Set the MOTOR CURRENT LIMIT and REGEN CURRENT
LIMIT trimpots to maximum (full CW).
3. Set the IR COMP trimpot to midrange (approximate 12
o’clock position).
4. Set the signal input (analog voltage signal or speed adjust
potentiometer) to zero.
5. Apply power to the drive.
6. Calibrate the trimpots as follows:
28
Calibration
250-0246r2_readers.qxd 6/7/01 10:51 AM Page 28