46
Symptom
Possible
Causes
Suggested
Solutions
Troubleshooting
Line fuse does not
blow, but the motor
does not run (cont.)
2. Speed adjust
potentiometer or
voltage input
signal not
connected to drive
input properly;
connections are
open.
3. Inhibit terminals
are jumpered.
4. S2 is shorted to S1
5. Drive is in current
limit.
6. Drive is not
receiving AC line
voltage.
2. Check connections
to input. Verify
that connections
are not open.
3. Remove jumper
from inhibit
terminal.
4. Remove short.
5. Verify that motor
is not jammed.
Increase MOTOR
CURR. LIMIT or
REGEN CURR.
LIMIT setting if
they are set too
low.
6. Apply AC line
voltage to L1 and
L2.