R410A Tropical Split Type Technical Manual
Troubleshooting
Duct Type
55
Operation lamp flashes:
Yes
No
No
Yes
Replace temperature sensor
Operation lamp flashing at 5Hz
Evaporate temperature sensor is abnormal.
Judge 1: Check evaporate temperature sensor is break off.
Judge 2: Evaporate temperature sensor is abnormal.
Validate: Check whether the resistance of the room
temperature sensor is correct according to Annex 1.
Replace temperature sensor
Replace indoor PCB.