Installation of Outdoor Units
R410A
Tropical Split Type Technical Manual
Installation
136
4. Heat Insulation of the Pipe
4.1 Heat Insulation of the Pipe
In order to prevent faults caused by condensate of the refrigerant pipe and drain pipe, perform condensate
prevention and heat insulation properly.
CAUTION:
If it is forecast that high humidity/temperature environment (condensate temperature is over 23
℃
) may exist in the ceiling, e.g.,
inside the ceiling with slab, ceiling which is in the same environment as the outdoor air), it is necessary to apply 10mm or thicker
adiabatic wool (16~20kg/m2 ) to the refrigerant pipe and the drain pipe in addition to applying the general heat insulation
materials. Enough heat insulation materials should also be applied to the refrigerant joint and the pipe joint.
4.2 Heat Insulation of the Drain Pipe
•
Be sure to entwine heat insulation materials round the drain pipe which runs through the room.
•
Carry through heat insulation for the drain pipes thoroughly.
4.3 Heat Insulation of the Refrigerant Pipe
•
Please use heat-resistant materials as heat insulation materials of the air-side pipe. (e.g., EPT)
•
Cover heat insulation materials separately at the liquid side and the air side. Moreover, perform heat
insulation thoroughly for the air-side pipes of the indoor unit, and prevent water from dripping outside the
unit.
Indoor unit
(air-side pipe)
Fig-26
•
After applying the auxiliary heat insulation materials, use vinyl resin tape to seal it lest water leak.
Summary of Contents for MFA-76CRN1
Page 34: ...34...
Page 74: ...74...
Page 91: ......
Page 100: ...96...
Page 104: ...Exploded View R410A Tropical Split Type Technical Manual 104 8 Exploded View 8 1 MOV 76CN1 C...
Page 106: ...Exploded View R410A Tropical Split Type Technical Manual 106 8 2 MOV 76HN1 C...
Page 108: ...Exploded View R410A Tropical Split Type Technical Manual 108 8 3 MOV 96CN1 C...
Page 110: ...Exploded View R410A Tropical Split Type Technical Manual 110 8 4 MOV 96HN1 C...
Page 112: ...Exploded View R410A Tropical Split Type Technical Manual 112 8 5 MOV 120CN1 C...
Page 114: ...Exploded View R410A Tropical Split Type Technical Manual 114 8 6 MOV 120HN1 C...