R410A
Tropical Split Type Technical Manual
Installation of Connective Pipe
Installation
139
b. Pull the pipe into the rear flare of the connective nut.
Fig-29
•
Tighten the nut
Align with the connective pipe
Screw up the connection pipe nut manually, and use a spanner to tighten it as shown in Fig-38
Fig-30
NOTE:
According to the installation conditions, too large torque will damage the flaring, and too small torque will lead to looseness and
leakage. Determine the tightening torque by reference to the following table.
•
Replenishment quantity of refrigerant required for air conditioner
The single-pass pipe is shorter than 5 m, and no additional length is required (note: The unit has been
replenished before being shipped).
If the single-pass pipe length is 5 m or more, the quantity of fluorine required to be replenished is 0.060X (L-5).
(Unit: kg)
Record the replenishment quantity of the refrigerant and keep the record properly for reference in future
maintenance.
Table 3:
Pipe diameter
Torque
φ
6.35
1420~1720N.cm
(144~176kgf.cm)
φ
9.53
3270~3990N.cm
(333~407kgf.cm)
φ
12.7
4950~6030N.cm
(504~616kgf.cm)
φ
16.0
6180~7540N.cm
(630~770kgf.cm)
φ
19.0
9720~11860N.cm
(990~1210kgf.cm)
Summary of Contents for MFA-76CRN1
Page 34: ...34...
Page 74: ...74...
Page 91: ......
Page 100: ...96...
Page 104: ...Exploded View R410A Tropical Split Type Technical Manual 104 8 Exploded View 8 1 MOV 76CN1 C...
Page 106: ...Exploded View R410A Tropical Split Type Technical Manual 106 8 2 MOV 76HN1 C...
Page 108: ...Exploded View R410A Tropical Split Type Technical Manual 108 8 3 MOV 96CN1 C...
Page 110: ...Exploded View R410A Tropical Split Type Technical Manual 110 8 4 MOV 96HN1 C...
Page 112: ...Exploded View R410A Tropical Split Type Technical Manual 112 8 5 MOV 120CN1 C...
Page 114: ...Exploded View R410A Tropical Split Type Technical Manual 114 8 6 MOV 120HN1 C...