Installation of Outdoor Units
R410A
Tropical Split Type Technical Manual
Installation
132
3.5.1 Size of Outdoor Unit Pipes and Piping Methods
1) Size of outdoor unit pipes and piping methods
Model
Gas side
Liquid side
MOV-76CN1-C
Φ
22
Φ
9.52
MOV-76HN1-C
Φ
22
Φ
9.52
MOV-96CN1-C
Φ
25
Φ
9.52
MOV-96HN1-C
Φ
25
Φ
9.52
MOV-120CN1-C
Φ
28.6
Φ
12.7
MOV-120HN1-C
Φ
28.6
Φ
12.7
2) Allowed length of refrigerant pipe and height difference (Fig-22)
Outdoor unit
Max. pipe length L 50m
H
e
ig
h
t
d
if
fe
re
n
c
e
b
e
tw
e
e
n
in
d
o
o
r
u
n
it
a
n
d
o
u
td
o
o
r
u
n
it
H
3
0
m
Indoor unit
Fig-22
Table 1:
76000 96000 50000
Btu/h
120000
Btu/h
Max. equivalent length of pipe (L)
50m
50m
Max. height difference
Height difference between
indoor unit and outdoor unit (H)
Outdoor upper
30m
30m
Outdoor lower
30m
30m
Summary of Contents for MFA-76CRN1
Page 34: ...34...
Page 74: ...74...
Page 91: ......
Page 100: ...96...
Page 104: ...Exploded View R410A Tropical Split Type Technical Manual 104 8 Exploded View 8 1 MOV 76CN1 C...
Page 106: ...Exploded View R410A Tropical Split Type Technical Manual 106 8 2 MOV 76HN1 C...
Page 108: ...Exploded View R410A Tropical Split Type Technical Manual 108 8 3 MOV 96CN1 C...
Page 110: ...Exploded View R410A Tropical Split Type Technical Manual 110 8 4 MOV 96HN1 C...
Page 112: ...Exploded View R410A Tropical Split Type Technical Manual 112 8 5 MOV 120CN1 C...
Page 114: ...Exploded View R410A Tropical Split Type Technical Manual 114 8 6 MOV 120HN1 C...