R410A Tropical Split Type Technical Manual
Troubleshooting
Duct Type
51
If the air conditioner fails and does not meet the above phenomena, check the system as the following table:
Symptoms
Causes
Handling methods
The unit does not
work
Power supply fails.
Operate after power resumes.
Power switch is not connected.
Connect the power supply properly.
Fuse blows out or circuit breaker snaps off.
Replace the fuse or check whether
electric leakage occurs.
The remote controller or the wire controller
fails.
Check the remote controller or wire
controller.
Air flowing
normally but
completely can’t
cooling
Temperature setting is improper.
Temperature setting is higher than the
room temperature in cooling mode. Or
temperature setting is lower than the
room temperature in heating mode.
3-minute protection of compressor.
Waiting for 3 minutes.
The unit starts or
stops frequently
The system is lack of refrigerant. Or there is
too much refrigerant in the system.
Fix the leakage places, and charge the
proper quantity of refrigerant.
Air or non-condensable gas exists in the
refrigerant system.
Vacuum the system and charge
refrigerant again.
Compressor fails.
Repair or replace the compressor.
The voltage is too high or too low.
Install a voltage regulator.
The refrigerant pipe is obstructed.
Locate and replace that part.
Poor cooling effect
The heat exchanger of outdoor unit or indoor
unit is too dirty.
Clean the heat exchanger.
The filter is too dirty.
Clean the filter.
Air inlet or air outlet of the indoor/ outdoor
unit is blocked.
Remove obstacles to keep well
ventilating.
Doors or windows of the room are open.
Close all the windows and doors.
Directly exposed to sunlight.
Use curtain to obstruct sunlight.
Too many heat sources in the room.
Reduce the heat sources.
The outdoor ambient temperature is too
high.
The cooling effect is poor but normal.
The system is lack of refrigerant.
Fix the leakage places, and charge the
proper quantity of refrigerant.
Poor heating
effect
The outdoor ambient temperature is lower
than -7
℃
.
Use an assistance heating device.
Doors or windows of the room are not closed
tightly.
Close the doors and windows properly.
The system is lack of refrigerant.
Fix the leakage places, and charge the
proper quantity of refrigerant.
Summary of Contents for MFA-76CRN1
Page 34: ...34...
Page 74: ...74...
Page 91: ......
Page 100: ...96...
Page 104: ...Exploded View R410A Tropical Split Type Technical Manual 104 8 Exploded View 8 1 MOV 76CN1 C...
Page 106: ...Exploded View R410A Tropical Split Type Technical Manual 106 8 2 MOV 76HN1 C...
Page 108: ...Exploded View R410A Tropical Split Type Technical Manual 108 8 3 MOV 96CN1 C...
Page 110: ...Exploded View R410A Tropical Split Type Technical Manual 110 8 4 MOV 96HN1 C...
Page 112: ...Exploded View R410A Tropical Split Type Technical Manual 112 8 5 MOV 120CN1 C...
Page 114: ...Exploded View R410A Tropical Split Type Technical Manual 114 8 6 MOV 120HN1 C...