Troubleshooting
R410A
Tropical Split Type Technical Manual
118
High pressure protection
Judge 1: Whether the wiring between the high pressure switch
and main control board is connected well or correctly
Judge 2: Whether the high pressure switch is broken
Yes
No
Connect it well
Validate: Short connect the high pressure switch
socket, check whether the system can run normally
Yes
Replace high pressure switch
No
Check whether the refrigerant system is ok
Replace outdoor PCB
No
Judge 3: Check whether the outdoor ambient temperature is too high
Yes
Stop the unit
No
Judge 4: Check whether the outdoor unit is bad ventilation
Yes
Make the outdoor unit ventilate well
No
Judge 5: Check whether the heat exchanger is dirty
Yes
Clean the heat exchanger
No
Judge 6: Check whether the refrigerant pipe is blocked
Yes
Drop refrigerant, then use the high
pressure nitrogen or refrigerant to
blow pipe, vacuumize and add the
refrigerant again
Summary of Contents for MFA-76CRN1
Page 34: ...34...
Page 74: ...74...
Page 91: ......
Page 100: ...96...
Page 104: ...Exploded View R410A Tropical Split Type Technical Manual 104 8 Exploded View 8 1 MOV 76CN1 C...
Page 106: ...Exploded View R410A Tropical Split Type Technical Manual 106 8 2 MOV 76HN1 C...
Page 108: ...Exploded View R410A Tropical Split Type Technical Manual 108 8 3 MOV 96CN1 C...
Page 110: ...Exploded View R410A Tropical Split Type Technical Manual 110 8 4 MOV 96HN1 C...
Page 112: ...Exploded View R410A Tropical Split Type Technical Manual 112 8 5 MOV 120CN1 C...
Page 114: ...Exploded View R410A Tropical Split Type Technical Manual 114 8 6 MOV 120HN1 C...