MC20-CEI
Doc. N°
MO-0431-ING
Microelettrica Scientifica S.p.A. - Copyright 2009
FW 1080.36.03.X
Date 18.11.2011
Rev.
3
Pag. 28
of 35
Display
Funzione
Tipo
Variabile
Default
Unità
Descrizione
Campo di
Regolazione
Passo
Stato
→
Abilit.
Enable of the protection function
Abilit/Disabil.
-
Opzioni
→
BI
Disabil.
Operation controlled by Blocking Digital Input
Abilit/Disabil.
-
Livelli
→
Io>>
0.9
Ion
Trip level
0.01 – 5.00
0.01
Io>>
Tempi
→
tIo>>
0.05
s
Trip time delay
0.05 – 60.00
0.01
Stato
→
Abilit.
Enable of the protection function
Abilit/Disabil.
-
Opzioni
→
BI
Disabil.
Operation controlled by Blocking Digital Input
Abilit/Disabil.
-
Io.1
1.00
%
Trip level
1 – 10
0.01
Uo.1
3.50
%
Trip level
1 – 40
0.01
aA.1
260
°
First angle trip sector
0 – 360
1
Livelli
→
aB.1
350
°
Second angle trip sector
0 – 360
1
67S1
Tempi
→
t67.1
1.00
s
Trip time delay
0.05 – 1.00
0.01
Stato
→
Abilit.
Enable of the protection function
Abilit/Disabil.
-
Opzioni
→
BI
Disabil.
Operation controlled by Blocking Digital Input
Abilit/Disabil.
-
Io.2
2.00
%
Trip level
1 – 10
0.01
Uo.2
3.50
%
Trip level
1 – 40
0.01
aA.2
100
°
First angle trip sector
0 – 360
1
Livelli
→
aB.2
280
°
Second angle trip sector
0 – 360
1
67S2
Tempi
→
t67.2
0.70
s
Trip time delay
0.05 – 1.00
0.01
Stato
→
Abilit.
Enable of the protection function
Abilit/Disabil.
-
Opzioni
→
Opz
NoScatto
Operation of output Relays on detection of
Internal Relay Fault
NoScatto –
Scatto
-
Livelli
→
Non Disp.
IRF
Tempi
→
Non Disp.
Stato
→
Abilit.
Enable of the protection function
Abilit/Disabil.
-
Opzioni
→
TrR
Relè1
Output relay operated on BF tripping
Relè1- Relè2
Relè3- Relè4
-
Livelli
→
Non Disp.
tBF
0.25
s
Trip time delay
0.05 – 0.75
0.01
AnIn
Tempi
→
tInc
0.25
s
C/B Discrepancy time
0.05 – 5.00
0.01
Stato
→
Abilit.
Enable of the protection function
Abilit/Disabil.
-
Opzioni
→
Non Disp.
Livelli
→
Non Disp.
TCS
Tempi
→
tTCS
1
s
Trip time delay
0.01 – 50
0.01
Stato
→
Non Disp.
Opzioni
→
BkL
Auto
Backlight
ON - OFF
-
Livelli
→
Non Disp.
LCD
Tempi
→
Non Disp.
Stato
→
Non Disp.
LBd
9600
Local Baud Rate
(Front panel RS232 communication speed)
9600 - 19200
38400 - 57600
-
RBd
9600
Remote Baud Rate (Rear panel terminal blocks
RS485 communication speed)
9600 - 19200
-
Mod
8,n,1
Remote mode (communication parameters)
Note: any change of this setting became valid
at the next power on
8,n,1
8,o,1
8,e,1
-
Opzioni
→
RPr
Modbus
Remote Protocol
Modbus
-
Livelli
→
Non Disp.
Comm
Tempi
→
Non Disp.
I Parametri possono essere programmati via porta seriale.