MC20-CEI
Doc. N°
MO-0431-ING
Microelettrica Scientifica S.p.A. - Copyright 2009
FW 1080.36.03.X
Date 18.11.2011
Rev.
3
Pag. 27
of 35
12.5.4 – Funzioni (
Functions
)
- “ Misure Istantanee “ (
Real Time Meas
)
- Press
to access (
Main Menu
)
- Select menu “ Regolaz.“ (
Read/Write
) by
- Press
- Select menu Funzioni” (
Functions
) by
- Press
- Select desired variables by
- Press
Stato
(Enable/Disable - Function)
Opzioni
(Options)
Livelli
(Trip Level)
- Select menu by
the menu
Tempi
(Trip time delay)
- Press
- Select desired variables by
- Press
- Insert Password if request (see § password)
- Press
- Select by
to set the new value
- Press
to validate the change and display show “Set Done!”
- Press
to go on Main Menu
Display
Funzione
Tipo
Variabile
Default
Unità
Descrizione
Campo di
Regolazione
Passo
Password
=
0000-9999
1111
-
Password for programming enable (see § Password)
Stato
→
Abilit.
Enable of the protection function
Abilit/Disabil.
-
TCC
D
Time Current Curves
D,A,B,C, I, VI, EI,
MI, SI
-
Opzioni
→
BI
Disabil.
Operation controlled by Blocking Digital Input
Abilit/Disabil.
-
Livelli
→
I>
0.50
In
Trip level
0.10 – 4.00
0.01
I>
Tempi
→
tI>
1.00
s
Trip time delay
0.05 – 60.00
0.01
Stato
→
Abilit.
Enable of the protection function
Abilit/Disabil.
-
Opzioni
→
BI
Disabil.
Operation controlled by Blocking Digital Input
Abilit/Disabil.
-
Livelli
→
I>>
0.9
In
Trip level
0.50 – 40.00
0.01
I>>
Tempi
→
tI>>
0.25
s
Trip time delay
0.05 – 60.00
0.01
Stato
→
Abilit.
Enable of the protection function
Abilit/Disabil.
-
Opzioni
→
BI
Disabil.
Operation controlled by Blocking Digital Input
Abilit/Disabil.
-
Livelli
→
I>>>
2.00
In
Trip level
0.50 – 40.00
0.01
I>>>
Tempi
→
tI>>>
0.05
s
Trip time delay
0.05 – 60.00
0.01
Stato
→
Abilit.
Enable of the protection function
Abilit/Disabil.
-
Opzioni
→
BI
Disabil.
Operation controlled by Blocking Digital Input
Abilit/Disabil.
-
Livelli
→
Io>
0.50
Ion
Trip level
0.01 – 4.00
0.01
Io>
Tempi
→
tIo>
0.50
s
Trip time delay
0.05 – 60.00
0.01