MC20-CEI
Doc. N°
MO-0431-ING
Microelettrica Scientifica S.p.A. - Copyright 2009
FW 1080.36.03.X
Date 18.11.2011
Rev.
3
Pag. 12
of 35
2.2.5.7 – 67S1 – First Directional Earth Fault protection level
Stato
(Status)
→
Abilit.
[Disabl.(
Disable
) / Abilit.(
Enable
)]
Opzioni
(Options)
→
BI
Disab.
[Disabl.(
Disable
) / Abilit.(
Enable
)]
Livelli
(Trip Level)
→
Io.1
1.00
%
(1
÷
10)
step
0.01
%
→
Uo.1
3.50
%
(1
÷
40)
step
0.01
%
→
aA.1
260
°
(0
÷
360)
step
1
°
→
aB.1
350
°
(0
÷
360)
step
1
°
Tempi
(Timer)
→
t67.1
1.00
s
(0.05
÷
1.00)
step
0.01
s
Stato
(Status)
:
If disable the function is disactivated
BI
:
Operation controlled by Blocking Digital Input
Io.1
:
Trip level
Uo.1
:
Trip level
aA.1
:
First angle trip sector
aB.1
:
Second angle trip sector
t67.1
:
Trip time delay
2.2.5.8 – 67S2 – Second Directional Earth Fault protection level
Stato
(Status)
→
Abilit.
[Disabl.(
Disable
) / Abilit.(
Enable
)]
Opzioni
(Options)
→
BI
Disab.
[Disabl.(
Disable
) / Abilit.(
Enable
)]
Livelli
(Trip Level)
→
Io.2
2.00
%
(1
÷
10)
step
0.01
%
→
Uo.2
3.50
%
(1
÷
40)
step
0.01
%
→
aA.2
100
°
(0
÷
360)
step
1
°
→
aB.2
280
°
(0
÷
360)
step
1
°
Tempi
(Timer)
→
t67.2
0.70
s
(0.05
÷
1.00)
step
0.01
s
Stato
(Status)
:
If disable the function is disactivated
BI
:
Operation controlled by Blocking Digital Input
Io.2
:
Trip level
Uo.2
:
Trip level
aA.2
:
First angle trip sector
aB.2
:
Second angle trip sector
t67.2
:
Trip time delay