MC20-CEI
Doc. N°
MO-0431-ING
Microelettrica Scientifica S.p.A. - Copyright 2009
FW 1080.36.03.X
Date 18.11.2011
Rev.
3
Pag. 26
of 35
12.5 - Regolazioni (
Programming / Reading the Relay Settings
)
-
“Main Menu “
-
select “Regolazioni“
-
select among following sub menus
12.5.1 - NodoCom (
Communication Address
)
-
“NodoCom“
-
“ Ind: # “
-
“ Password ???? “
(if not yet entered; see § Password)
-
to select the Address (1-250)
-
to validate.
Set Done!
The default address is 1.
Display
Description
Setting Range
Step
Unit
Ind:
1
Identification number for connection on serial communication bus
1 -
250
1
-
12.5.2 – Data/Ora (
Time/Date
)
-
“Data/Ora“
Date: Current Date, Time: Current time
-
“20YY/…… “
to set year,
-
“20XX/MM“
to set month,
-
“20XX/XX/DD“
to set day,
-
“20XX/XX/XX“
-
“hh/mm“
to set hour,
-
“XX/mm“
to set minutes,
-
To validate
Set Done!
-
Exit
12.5.3 – Val.Nom. (
Rated Input Values
)
-
“Val.Nom.“
Rated Input Values
-
1
st
Variable
-
to scroll variables
-
to modify selected variable
-
“ Password ???? “
(if not yet entered) or #??? (if not yet entered; see §
Password)
-
to set variable value,
-
to validate.
Set Done!
Display
Description
Setting Range
Step
Unit
In
300
A
Reference primary current of the relay
1 - 9999
1
A
I1
300
A
Rated Primary current of phase C.T.
1 - 9999
1
A
I2
5
A
Rated Secondary current of phase C.T.
1 -
5
1/5
A
Io1
100
A
Rated Primary current of the tore C.T. detecting earth fault
current.
1 - 9999
1
A
Io2
1
A
Rated secondary current of the tore C.T. detecting earth fault
current.
1 -
1
-
A
Vo1
10
kV
Rated primary voltage of VT phase to neutral
0.05 -
500
0.01
kV
Vo2
100
V
Rated secondary voltage of VT phase to neutral
50 -
115
0.01
V
Freq
50
Hz
System rated frequency
50 -
60
10
Hz