17.7 - Function:
1I>
(First Overcurrent Element F50/51)
Status
→
Enab.
No
[No / Yes]
Options
→
f(t)
Type - D
[D / A / B / C / I / VI / EI / MI / SI ]
→
tBI
Off
[Off / 2tBO]
Oper. Levels
→
Is
1
In
(0.1
÷
4)
step 0.01 In
Timers
→
ts
5
s
(0.02
÷
100)
step
0.01 s
→
tBO
0.75
s
(0.05
÷
0.75)
step
0.01 s
17.7.1 - Description of variables
Enab.
: Function enabling (No = Disable / Yes = Enable)
f(t)
: Operation characteristic (Time/Current curve):
(D)
= Independent definite time
(A)
= IEC Inverse Curve type A
(B)
= IEC Very Inverse Curve type B
(C)
= IEC Extremely Inverse Curve type C
(I)
= IEEE Inverse Curve
(VI)
= IEEE Very Inverse Curve
(EI)
= IEEE Extremely Inverse Curve
(MI)
= IEEE Moderate Inverse Curve
(SI)
= IEEE Short Inverse Curve
tBI
: Blocking input reset time
Off
= Permanent block
2tBO
= Set 2xtBO.
Is
: Minimum operation level
ts
: Trip time delay
tBO
: Time to reset of the Blocking Output after expiring of the Trip time delay. “tBO”
is also the trip time delay of the Breaker Failure function.