17.15.2.1 - Example
Example: programming of the Reclose Shots initiated by tripping of the protection function 1I>.
R 1I>
=
Recl.Dis.
:
no shot is initiated on tripping of the function 1I>.
R 1I>
=
1
:
only the shot n°1 of the AR cycle is initiated on tripping of the function
1I>.
R 1I>
=
1+2
:
only the shots n°1 and 2 of the AR cycle are initiated on tripping of the
function 1I>.
R 1I>
=
1+2+3
:
only the shots n°1 and 2 and 3 of the AR cycle are initiated on tripping
of the function 1I>.
R 1I>
=
1+2+3+4
:
all the shots n°1 and 2 and 3 and 4 of the AR cycle are initiated on
tripping of the function 1I>.
R RT
=
Recl.Dis.
:
no shot is initiated on Remote Trip signal (RT).
R RT
=
1
:
only the shot n°1 of the AR cycle is initiated on Remote Trip signal
(RT).
R RT
=
1+2
:
only the shots n°1 and 2 of the AR cycle are initiated on Remote Trip
signal (RT).
R RT
=
1+2+3
:
only the shots n°1 and 2 and 3 of the AR cycle are initiated on Remote
Trip signal (RT).
R RT
=
1+2+3+4
:
all the shots n°1 and 2 and 3 and 4 of the AR cycle are initiated on
Remote Trip signal (RT).
Similarly for the other variables (R 2I>, R 3I>, R 1Io>, R 2Io>, R 3Io>, R 1Uo>, R 2Uo>).