MC2-30T
Doc. N°
MO-0483-ING
Copyright 2016
Date
17.03.2022
Rev.
2
Pag. 25
of
70
15.1 – Events on display
Functions
Events
Displayed
Events Description
Status
T>
Tal
Tal
Alarm Thermal Image
Rise
T>
T>
Trip
Rise
Fall
1I>
1I>
1I>
Start
Fist overcurrent element
Rise
t1I>
t1I>
Trip
Rise
Fall
2I>
2I>
2I>
Start
Second overcurrent element
Rise
t2I>
t2I>
Trip
Rise
Fall
3I>
3I>
3I>
Start
Third overcurrent element
Rise
t3I>
t3I>
Trip
Rise
Fall
1Io>
1Io>
1Io>
Start
Fist earth fault element
Rise
t1Io>
t1Io> Trip
Rise
Fall
2Io>
2Io>
2Io>
Start
Second earth fault element
Rise
t2Io>
t2Io> Trip
Rise
Fall
3Io>
3Io>
3Io>
Start
Third earth fault element
Rise
t3Io>
t3Io> Trip
Rise
Fall
1Is>
1Is>
1Is>
Start
First negative sequence current
Rise
t1Is>
t1Is> Trip
Rise
Fall
2Is>
2Is>
2Is>
Start
Second negative sequence current
Rise
t2Is>
t2Is> Trip
Rise
Fall
TCS
TCS
TCS
Start
Trip Coil Supervision
Rise
tTCS
tTCS
Trip
Rise
Fall
IRF
IRF
IRF
Start
Internal Relay Failure
Rise
tIRF
tIRF
Trip
Rise
TimeSincro
Time synchronization
Rise
Disk
DskClean
Disk near to full clean operation is required
Rise
DskFull
Disk full write should be lock
Rise
L/R disc
Local/Remote signal Discrepancy
Rise
C/B
manOpKey
Circuit Breaker intentional open by key
Rise
manOpLocC
Circuit Breaker intentional open by local command
Rise
manOpRemC
Circuit Breaker intentional open by remote command
Rise
manOpExtIn
Circuit Breaker intentional open by external input
Rise
ExterManOp
Circuit Breaker intentional external open
Rise
manClKey
Circuit Breaker intentional close by key
Rise
manClLocC
Circuit Breaker intentional close by local command
Rise
manClRemC
Circuit Breaker intentional close by remote command
Rise
manClExtIn
Circuit Breaker intentional close by external input
Rise
ExterManCh
Circuit Breaker intentional external close
Rise
CB-Fail
Circuit Breaker (C/B Failure)
Rise
Fall
R
ecl
osu
re
79 X
Recloser command
Rise
FR
Recloser Failure
Rise
CRC
Recloser cycle in progress
Rise
TWR
Trip without recloser
Rise
ReclDone
Recloser succesfull
Rise
StartTnExt
Start reclaim time [TrExt] on external lockout
Rise
Stop TrExt
Reclaim time expiration [TrExt] on external lockout
Rise
RCLInterr.
RCL interrupted by setUp cause (no trip Enable)
Rise
CH-Riusc.
Manual close succesfull
Rise
BiRCL
Presence Reclosure external lockout cause
(input/CB Failure)
Rise
Fall
Start R1
Start first (1°) recloser cycle (Start t1)
Rise
Start R2
Start second (2°) recloser cycle (Start t2)
Rise
Start R3
Start third (3°) recloser cycle (Start t3)
Rise
Start R4
Start fourth (4°) recloser cycle (Start t4)
Rise
StartTr-d1
Start Reclaim&Discrim. time on 1° close (tr1-td1)
Rise
CRIntScDis
Cycle blocked by not reclosing trip
Rise
CRIntApInt
Cycle blocked byintentional CB open
Rise
CRIntBinp
Cycle interrupted by external cause
Rise
StartTr-d2
Start Reclaim&Discrim. time on 2° close (tr2-td2)
Rise
StartTr-d3
Start Reclaim&Discrim. time on 3° close (tr3-td3)
Rise
StartTr4
Start Reclaim time on 4° close (tr4)
Rise
CRCInChCB
Cycle blocked intentional CB Close
Rise
StartRChM
Start manual recloser cycle
Rise
FrLTr
Trip in last reclaim time available
Rise
Gr1-Gr2
Switch to SetUp Group2
Rise
Fall
RCLInterr.
RCL interrupt by persistent fault
Rise
SeqC
Sequence Coordination (Start new/next RCL cycle )
Rise