Type: P9680

Type: P9680

Type: P9680

Type: P9680    

Combined Overcurrent and Earth Fault Relay

Combined Overcurrent and Earth Fault Relay

Combined Overcurrent and Earth Fault Relay

Combined Overcurrent and Earth Fault Relay    

 

 

True R.M.S. measurements 

 

Low Set and High Set tripping thresholds for both Overcurrent and Earth Fault detection 

 

6 selectable IDMT (Inverse Definite Minimum Time) characteristic curves  

 

Adjustable DT (Definitive Time)  

 

Three phase over current and earth fault detection with live display of individual phase and earth fault currents 

 

Last trip memory (last 10 trips stored and can be recalled) 

 

Pre-defined selectable CT ratio’s (5:5….6000:5) 

 

Microprocessor based (self checking) with non-volatile memory 

 

“Ecosmart” Energy efficient power supply design 

 

Rear mounted pluggable connectors for supply, relay contacts and current inputs 

 

 
 
      

 

  
  
 
                                                                                                                                                                                                                                                                       
 
 
 

 
 
 
 
 

 

 
 
 
 
 
 
 
 
 
 
 
 

 

OPERATION & OVERVIEW 

 

The 

P9680 

P9680 

P9680 

P9680 

(from the P9600 series family of IDMT/DT relays) is a microprocessor based relay 

designed to monitor and detect Overcurrent on individual phases and non-directional Earth faults (by 
measurement of the neutral current) in 3-phase applications. Typically the

    P9680 

P9680 

P9680 

P9680 

is wired in 

conjunction with external current transformers of the feeder to be protected. 

 

A clear backlit LCD provides all key information the user requires for both operation and setting up. 
Setting is achieved in a few simple steps and requires no previous knowledge of product operation. 

 

Normal operation provides the user with actual live individual phase currents and earth fault current 
all on one screen. The actual phase current represents that of the current passing through the 
primary side of the externally connected CT’s. This is achieved by the setting of the ratio for the CT.  

 

Programming mode allows the user to assign the operation mode for both internal relays. They can 
be individually assigned to Overcurrent, Earth fault or a combination of both. They can also be 
configured for Auto or Manual resetting. Relay 2 has the added option of being allowed to energise 
at the start or end of a time out period. If assigned to energise at the start, the Relay can be used to 
operate a buzzer or lamp giving early warning before a system actually shuts down. 

 

Low-set and High-set thresholds can be programmed for both Overcurrent and Earth fault 
detection. The time current characteristic of the low-set units are selectable between Normal 
Inverse curve 3/10, Normal Inverse curve 1.3/10, Long Time Inverse curve, Very Inverse curve, 
Extremely Inverse curve, Extremely Inverse 0.65 curve and Definite Time. High-set units are the 
Definitive Time type. Instantaneous tripping is possible by setting the time to minimum. 

 

Two simple Summary screens are displayed once the programming is complete. The same screens 
can also be displayed by presses of the 

“RESET” 

button. This allows the user to access key 

information with the tamperproof transparent cover closed and sealed. 

 

A Test mode is provided (also accessible with tamperproof transparent cover closed) to confirm the 
correct operation of the internal relays. The relays will energise when the 

“TEST”

 button is pressed 

and de-energise when the button is released (AUTO Reset) or when the 

“RESET”

 button is pressed 

(MAN Reset). 

 

Following a trip condition, the information about the trip is then stored. This can then be recalled 
later if required using the 

“RESET” 

button to access the information. The 

P9680

P9680

P9680

P9680

 has the ability to 

store up to 10 trips and using the “Up” and “Down” buttons, allows each trip to be displayed 
individually. Each trip is also marked with a time stamp showing the time from power up as well as 
the time from the previous trip. This feature is very useful for establishing a pattern on particular 
inputs, knowing when they occurred and how frequent! 
 

 
 

 

FUNCTION OVERVIEW 

 

Programming mode. 

 
 
 
 
 
 
 
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
             Programmable parameters 
 

User settings summary mode 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 

1

 Summary screens are split into two with one screen showing Overcurrent settings and the 

other showing Earth fault settings. 

2

 Displaying of the Summary screens during normal operation is achieved via subsequent 

presses of the “RESET” button. See Section 8. QUICK VIEW OF USER SETTINGS 
for further information. 

 

PRESENTATION

 

 

 

 
 

 

    

    

    

    
    
    
    
    

 

  

 

    
    
    

1. LCD (Liquid Crystal Display) for user information     5. 

“MODE” 

button* 

2. 

“RESET”

 button                                   6. Parameter increment button* 

3. 

“TEST”

 button                                    7. Parameter decrement button* 

4. 

“Power supply”

 green LED indication               8. 

“Trip status” 

red LED indication 

                                                      * accessible only when the front cover is open 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

START 

TOROID RATIO 

Set ratio of externally 

connected toroids

 

 

NETWORK 

FREQUENCY 

Set for 50 or 60Hz 

connected toroids

 

RELAY 1 SETTING 

Assign monitoring function 

and set reset mode method 

RELAY 2 SETTING 

Assign monitoring function, 

relay activation and reset 

mode methods 

OVERCURRENT 

SETTING 

Set Low-set and High-set 

tripping parameters 

EARTH FAULT 

CURRENT SETTING 

Set Low-set and High-set 

tripping parameters 

 

SUMMARY

1

 

List all parameter and 

function settings

 

 

START 

Display live individual 

phase currents and 

earth fault current 

SUMMARY

1 2

 

List all parameter and 

function settings

 

Dims: 

W x H. 96 x 96mm (front) 

W x H. 89.5 x 89.5mm (main body) 

L. 100mm 

 

I

L1

 

 

0.00

A

 

I

L2

 

 

0.00

A

 

I

L3

 

 

0.00

A    

 

I

  

0.00

A    

 

‰

 

 

 

Summary of Contents for P9680

Page 1: ...or both Overcurrent and Earth fault detection The time current characteristic of the low set units are selectable between Normal Inverse curve 3 10 Normal Inverse curve 1 3 10 Long Time Inverse curve Very Inverse curve Extremely Inverse curve Extremely Inverse 0 65 curve and Definite Time High set units are the Definitive Time type Instantaneous tripping is possible by setting the time to minimum ...

Page 2: ...occurred continued on next page INSTALLATION BEFORE INSTALLATION ISOLATE THE SUPPLY THIS PRODUCT IS DESIGNED TO CONNECT TO SEVERAL TYPES OF CIRCUITS ENSURE ALL ARE ISOLATED Remove the P9680 P9680 P9680 P9680 from the packaging Lift the raised part of the side clip in order to withdraw from the housing Carry this out on each side Insert the P9680 P9680 P9680 P9680 into the panel cut out and fit the...

Page 3: ...TTING Default setting for Relay 2 is linked to O C E F and energising at the end of the time out period Resetting mode is Auto Setting of Relay 2 is carried out in a similar manner as Relay 1 however it is necessary to assign the relay to either energise at the start S or end E of the time out period Actual LCD presentation when adjustable parameters are displayed Press and hold the button to set ...

Page 4: ...further button presses are made If a trip condition occurs whilst in this mode the screen will automatically change to display the information relating to the current status As described in Section 8 use the to gain access to the Last Tripped Information screen The display will show the most recent trip information as follows If more than one trip event is stored use the and buttons to select the ...

Page 5: ...een cleared The LCD reverts back to displaying the normal system currents and the red Tripp Tripp Tripp Tripped ed ed ed LED stops flashing If either relay is set for Auto resetting then they would have de energised after the fault had cleared The corresponding relay ident i e R1 and or R2 on the display would also disappear Pressing the RESET RESET RESET RESET button will only clear the LCD If ei...

Page 6: ...0 05 t t t t s s s s 10 1 0 1 0 01 t t t t s s s s Normal Inverse 3 10 Normal Inverse 3 10 Normal Inverse 3 10 Normal Inverse 3 10 NI 3 10 NI 3 10 NI 3 10 NI 3 10 t t t t s s s s k k k k 1 0 0 9 0 8 0 7 0 6 0 5 0 4 0 3 0 2 0 1 0 05 10 1 0 1 1 10 20 I I I I I I I I Long Time Inverse Long Time Inverse Long Time Inverse Long Time Inverse LTI LTI LTI LTI 200 100 10 1 0 1 k k k k 1 0 0 9 0 8 0 7 0 6 0 ...

Page 7: ...e Un 1 2 85 265VAC 85 370VDC1 18 55VAC 18 72VDC Voltage range should be specified at time of ordering Rated frequency 50 60Hz AC Supplies Isolation Over voltage cat III Rated impulse withstand voltage 1 4kV 1 2 50µS IEC 60664 Power consumption 3W max If connecting a fuse externally a Time Delay type is recommended with a rating of 0 5A or higher Rated current input In 5A directly connected Rated f...