Page 34
Installation
optoNCDT 1220
5.4.9
Sensor Cable
2 m
ILD 1220 with open ends
Never fall below the bending radius for the sensor cable of 30 mm (fixed) or 60 mm (dynamic).
i
The fixed connected sensor cables are not cable carriers suitable.
i
Unused open cable ends must be insulated to protect against short circuits or malfunction of the sen-
sor.
Avoid excessive pulling to the cables.
Provide strain relieves near the connectors when cables > 5 m are
vertically free hanging.
Connect the cable shield to the potential equalization (PE, protective earth conductor) on the evaluator
(control cabinet, PC housing) and avoid ground loops.
Never lay signal leads next to or together with power cables or pulse-loaded cables (e.g. for drive units
and solenoid valves) in a bundle or in cable ducts. Always use separate ducts.
Recommended strand cross-section for self-made connection cables: ≥ 0.14 mm² (AWG 25).