Page 31
Installation
optoNCDT 1220
5.4.5
RS422 Connection with USB Converter IF2001/USB
Cross the lines for connections between sensor and PC.
i
Disconnect or connect the D-sub connection between RS422 and USB converter when the sensor is disconnected from power
supply only.
Sensor
End device (converter)
Type IF2001/USB
from MICRO-EPSILON
Symmetric differential signals acc. to
EIA-422, not galvanically isolated from
supply voltage.
Use a shielded cable with twisted
cores.
Signal
Sensor cable
Tx +
grey
Rx + (Pin 3)
Tx -
pink
Rx -(Pin 4)
Rx +
green
Tx + (Pin 1)
Rx -
yellow
Tx -(Pin 2)
GND
blue
GND (Pin 9)
Fig. 15 Pin assignment IF2001/USB
5.4.6
Analog Output
The sensor provides a current output 4 ... 20 mA.
i
The output may not be continuously operated in short circuit operation without load resistor. The short circuit operation leads to
durable thermal overload and thus for automatic overload shutdown of the output.
Connect the white and the blue wire on the sensor to a measuring device.
Sensor
white
U
out
R
C
100 nF
blue
ILD1220
I
out
11...
30 VDC
With the adjacent circuit you will get an analog
voltage output in the range of 1 ... 5 V.
R
= 250 Ohm:
U
OUT
1 ... 5 V at
U
B
> 11 V
R
= 500 Ohm:
U
OUT
2 ... 10 V at
U
B
> 17 V
Signal
Sensor cable
I
OUT
white
GND
blue
Fig. 16 Wiring for voltage output