P341 Technical Data Sheet
33
P341 Software versions 36 & 71J
CLI1 I< Alarm (4…20 mA input only):
Disabled/Enabled
CLI1 I< Alm Set (4…20 mA input only):
0.0…4.0 mA
CLI2/3/4 as CLI1
Current loop output
CLO1 Output 1: Disabled/Enabled
CLO1 Output Type:
0 - 1 mA
0 - 10 mA
0 - 20 mA
4 - 20 mA
CLO1 Set Values: Primary/Secondary
CLO1 Parameter: As shown below*
CLO1 Min: Range, step size and unit
corresponds to the selected parameter
CLO1 Max: Same as CLO1 Min
CLO2/3/4 as CLO1
Current Loop Output Parameters
Current Magnitude:
IA Magnitude
IB Magnitude
IC Magnitude
IN Derived Mag: 0.00…16.0 A
I Sen Mag: 0.00… 2.0 A
Phase Sequence Components:
I1 Magnitude
I2 Magnitude
I0 Magnitude:
0.00…16.0 A
Phase Currents:
IA RMS*
IB RMS*
IC RMS*
0.00…16.0 A
P-P Voltage Magnitude:
VAB Magnitude
VBC Magnitude
VCA Magnitude
0.0…200.0 V
P-N Voltage Magnitude:
VAN Magnitude
VBN Magnitude
VCN Magnitude
0.0…200.0 V
Neutral Voltage Magnitude:
VN1 Measured Mag
VN Derived Mag
0.0…200.0 V
Phase Sequence Voltage Components:
V1 Magnitude*
V2 Magnitude
V0 Magnitude
0.0…200.0 V
RMS Phase Voltages:
VAN RMS*
VBN RMS*
VCN RMS*
0.0…200.0 V
Frequency: 0.00…70.0 Hz
3 Phase Watts*: -6000 W…6000 W
3 Phase Vars*: -6000 Var…6000 Var
3 Phase VA*: 0…6000 VA
3Ph Power Factor*: -1…1
Single Phase Active Power:
A Phase Watts*:
B Phase Watts*:
C Phase Watts*:
-2000 W…2000 W
Single Phase Reactive Power:
A Phase Vars*:
B Phase Vars*:
C Phase Vars*
-2000 Var…2000 Var
Single Phase Apparent Power:
A Phase VA*:
B Phase VA*:
C Phase VA*
0…2000 VA
Single Phase Power Factor:
Aph Power Factor*
BPh Power Factor*
CPh Power Factor*
-1…1
3 Phase Current Demands:
IA Fixed/Roll/Peak Demand*
IB Fixed/Roll/Peak Demand*
IC Fixed/Roll/Peak Demand*
0.00…16.0 A
3ph Active Power Demands:
3Ph W Fix/Roll/Peak Demand*
-6000W…6000W
3ph Reactive Power Demands:
3Ph Vars Fix/Roll/Peak Dem*
-6000 Var…6000 Var
Thermal Overload: 0.00…200.0%
CL Input 1-4: -9999…9999.0
DLR Ampacity: 0.00…4.0 A
Maximum ac current: 0.00…16.0 A
df/dt: -10.00…10.00 Hz/s
Check Synch Voltages: 0.0…200.0 V
Slip Frequency: 0.00…70.00 Hz
Note 1:
Measurements marked with an
asterisk, the internal refresh rate is
nominally 1 s, others are 0.5 power
system cycles or less.
Note 2:
The polarity of Watts, Var and power
factor is affected by the measurements
Mode
setting.
Note 3:
These settings are for nominal 1 A and
100/120 V versions only. For other
versions they need to be multiplied
accordingly.
Summary of Contents for ALSTOM P341
Page 3: ......
Page 4: ...0 0 12 3 12 3 4...
Page 5: ......
Page 6: ...00 01 1 2 33 1 3 30 30 4...
Page 7: ...0 1 2 0 0 3 4 5 2 12 3 4 6 3 5 1 0 3 0...
Page 8: ...0 10 2 0 13 4 2 1 2 3 5 6 6 7 8 8 7 6 9...
Page 9: ...0 1 2 3 3 234 34 5 6 5 75 8 9...
Page 10: ...01 21 3 1 4 56 1 0 31 0 31 0 31 7 8 6 9 1 2 3 31 121 7 9 8 6...
Page 61: ......