P341 Technical Data Sheet
23
P341 Software versions 36 & 71J
CT and VT ratios
Main VT Primary:
100...1000000 V
Main VT Sec'y:
80...140
(100/120 V) 320…560 V (380/480 V)
C/S VT Primary:
100 V…1 MV
C/S VT Secondary:
80…140 V
VN VT Primary (P342/3): 100…1000000 V
VN VT Secondary (P342/3):
80…140 V
(100/120 V) 320…560 V (380/480 V)
PH CT Polarity:
Standard, Inverted
Phase CT Primary:
1 A…50 kA
Phase CT Sec'y Sec'y : 1 A/5 A
ISen CT Polarity:
Standard/Inverted
ISen CT Primary:
1 A…60 KA
ISen CT Sec’y:
1 A/5 A
Sequence of event recorder (record
control)
Alarm Event:
Disabled/Enabled
Relay O/P Event:
Disabled/Enabled
Opto Input Event:
Disabled/Enabled
General Event:
Disabled/Enabled
Fault Rec Event:
Disabled/Enabled
Maint Rec Event:
Disabled/Enabled
Protection Event:
Disabled/Enabled
DDB 31 - 0:
(up to):
DDB 2047 - 2016:
Binary function link strings, selecting which
DDB signals will be stored as events, and
which will be filtered out.
Oscillography
(disturbance recorder)
Duration: 0.10…10.50
s
Trigger Position:
0.0…100.0%
Trigger Mode:
Single/Extended
Analog Channel 1:
(up to):
Analog Channel 8:
Disturbance channels selected from:
IA/IB/IC/VA/VB/VC/VN/ISensitive/Frequency
V Checksync
Digital Input 1:
(up to):
Digital Input 32:
Selected binary channel assignment from
any DDB status point within the relay (opto
input, output contact, alarms, starts, trips,
controls, logic…).
Input 1 Trigger: No Trigger/Trigger/LH (Low to
High)/Trigger H/L (High to Low)
(up to):
Input 32 Trigger: No Trigger/Trigger
L/H/Trigger H/L
Measured operating data
(measure’t setup)
Default Display:
Access Level
3Ph + N Current
3Ph Voltage
Power
Date and Time
Description
Plant Reference
Frequency
Local Values:
Primary/Secondary
Remote Values:
Primary/Secondary
Measurement Ref:
VA/VB/VC/IA/IB/IC
Measurement Mode:
0/1/2/3
Fix Dem Period:
1…99 mins
Roll Sub Period:
1…99 mins
Num Sub Periods:
1…15
Remote2 Values:
Primary/Secondary
Communications
RP1 Address:
(Courier or IEC
870-5-103)
:
0…255
RP1 Address:
(DNP3.0):
0…65534
RP1 Address:
(MODBUS):
1…247
RP1 InactivTimer:
1…30 mins
RP1 Baud Rate:
(IEC
870-5-103):
9600/19200 bits/s
RP1 Baud Rate:
(MODBUS, Courier):
9600/19200/38400 bits/s
RP1 Baud Rate:
(DNP3.0):
1200/2400/4800/9600/19200/ 38400 bits/s
RP1 Parity:
Odd/Even/None
(MODBUS, DNP3.0)
RP1 Meas Period:
1…60 s
(IEC
870-5-103)
RP1 PhysicalLink:
Copper (EIA(RS)485/K bus) or Fiber Optic
RP1 Time Sync:
Disabled/Enabled
MODBUS IEC Timer: Standard/Reverse
RP1 CS103Blocking:
Disabled
Monitor Blocking
Command Blocking
RP1 Port Config:
(Courier):
K Bus
EIA485 (RS485)
RP1 Comms Mode:
(Courier):
IEC 60870 FT1.2
IEC 60870 10-Bit No parity
Note:
If RP1 Port Config is K Bus the baud
rate is fixed at 64 kbits/s
Optional Ethernet port
NIC Tunl Timeout: 1...30 mins
NIC Link Report: Alarm, Event, None
NIC Link Timeout: 0.1...60 s
Optional additional second rear
communication (rear Port2 (RP2))
RP2 Port Config:
EIA(RS)232
EIA(RS)485
K-Bus
Summary of Contents for ALSTOM P341
Page 3: ......
Page 4: ...0 0 12 3 12 3 4...
Page 5: ......
Page 6: ...00 01 1 2 33 1 3 30 30 4...
Page 7: ...0 1 2 0 0 3 4 5 2 12 3 4 6 3 5 1 0 3 0...
Page 8: ...0 10 2 0 13 4 2 1 2 3 5 6 6 7 8 8 7 6 9...
Page 9: ...0 1 2 3 3 234 34 5 6 5 75 8 9...
Page 10: ...01 21 3 1 4 56 1 0 31 0 31 0 31 7 8 6 9 1 2 3 31 121 7 9 8 6...
Page 61: ......