P341 Technical Data Sheet
11
P341 Software versions 36 & 71J
Power-up time
Time to power up < 11 s.
Power supply interruption
3 power supply options:
(i) Vx: 24 to 48 V dc
(ii) Vx: 48 to 110 V dc, 40 to 100 V ac (rms)
(iii) (i) Vx: 110 to 250 V dc, 100 to 240 V ac
(rms)
Per IEC 60255-11: 2008
The relay will withstand a 100% interruption in
the DC supply without de-energizing as
follows:
(i) Vx: 24 to 48 V dc
Quescent / half load
20 ms at 24 V
50 ms at 36 V
100 ms at 48 V
maximum loading:
20 ms at 24 V
50 ms at 36 V
100 ms at 48 V
(ii) Vx: 48 to 110 V dc
Quescent / half load
20 ms at 36 V
50 ms at 60 V
100 ms at 72 V
200 ms at 110 V
maximum loading:
20 ms at 36 V
50 ms at 60 V
100 ms at 85 V
200 ms at 110 V
(iii) (i) Vx: 110 to 250 V dc
Quescent / half load
50 ms at 110 V
100 ms at 160 V
200 ms at 210 V
maximum loading:
20 ms at 85 V
50 ms at 98 V
100 ms at 135 V
200 ms at 174 V
Per IEC 60255-11: 2008:
The relay will withstand an interruption in the
AC supply without de-energizing as follows:
(ii) Vx = 40 to 100 V ac
Quescent / half load
50 ms at 27 V for 100% voltage dip
maximum loading:
10 ms at 27 V for 100% voltage dip
(iii) Vx = 100 to 240 V ac
Quescent / half load
50 ms at 80 V for 100% voltage dip
maximum loading:
50 ms at 80 V for 100% voltage dip
Maximum loading = all digital inputs/outputs
energized
Quescent or 1/2 loading = 1/2 of all digital
inputs/outputs energized
Battery backup
Front panel mounted
Type ½ AA, 3.6 V Lithium Thionyl Chloride
Battery (SAFT advanced battery reference
LS14250)
Battery life (assuming relay energized
for 90% time) >10 years
Field voltage output
Regulated 48 Vdc
Current limited at 112 mA maximum output
Operating range 40 to 60 V
Digital (“Opto”) inputs
Universal opto inputs with programmable
voltage thresholds (24/27, 30/34, 48/54,
110/125, 220/220 V). May be energized from
the 48 V field voltage, or the external battery
supply.
Rated nominal voltage: 24 to 250 Vdc
Operating range: 19 to 265 Vdc
Withstand: 300 Vdc, 300 Vrms.
Nominal pick-up and reset thresholds:
Nominal battery 24/27: 60 - 80% DO/PU
(logic 0) <16.2
(logic 1) >19.2
Nominal battery 24/27: 50 - 70% DO/PU
(logic 0) <12.0
(logic 1) >16.8
Nominal battery 30/34: 60 - 80% DO/PU
(logic 0) <20.4
(logic 1) >24.0
Nominal battery 30/34: 50 - 70% DO/PU
(logic 0) <15.0
(logic 1) >21.0
Nominal battery 48/54: 60 - 80% DO/PU
(logic 0) <32.4
(logic 1) >38.4
Nominal battery 48/54: 50 - 70% DO/PU
(logic 0) <24.0
(logic 1) >33.6
Nominal battery 110/125: 60 - 80% DO/PU
(logic 0) <75.0
(logic 1) >88.0
Nominal battery 110/125: 50 - 70% DO/PU
(logic 0) <55.0
(logic 1) >77.0
Nominal battery 220/250: 60 - 80% DO/PU
(logic 0) <150.0 (logic 1) >176.0
Nominal battery 220/250: 50 - 70% DO/PU
(logic 0) <110 (logic 1) >154
Recognition time:
<2 ms with long filter removed,
<12 ms with half cycle ac immunity filter on
Output contacts
Standard contacts
General purpose relay outputs for signaling,
tripping and alarming:
Continuous Carry Ratings (Not Switched):
Maximum continuous current: 10 A (UL: 8 A)
Short duration withstand carry: 30 A for 3 s
Summary of Contents for ALSTOM P341
Page 3: ......
Page 4: ...0 0 12 3 12 3 4...
Page 5: ......
Page 6: ...00 01 1 2 33 1 3 30 30 4...
Page 7: ...0 1 2 0 0 3 4 5 2 12 3 4 6 3 5 1 0 3 0...
Page 8: ...0 10 2 0 13 4 2 1 2 3 5 6 6 7 8 8 7 6 9...
Page 9: ...0 1 2 3 3 234 34 5 6 5 75 8 9...
Page 10: ...01 21 3 1 4 56 1 0 31 0 31 0 31 7 8 6 9 1 2 3 31 121 7 9 8 6...
Page 61: ......