P341 Technical Data Sheet
25
P341 Software versions 36 & 71J
Protection functions
System config.
Phase Sequence: Standard ABC/Reverse
ACB
VT Reversal: No Swap/A-B Swapped/B-C
Swapped/C-A Swapped
CT Reversal: No Swap/A-B Swapped/B-C
Swapped/C-A Swapped
C/S Input: A-N, B-N, C-N, A-B, B-C, C-A
C/S V Ratio Corr: 0.500...2.000
Main VT Vect Grp: 0...11
Main VT Location: Gen/Bus
Reverse/low forward/overpower
Operating mode:
Generating
Motoring
Power 1 Function:
Reverse
Low forward
Over
-P>1 Setting (reverse power/P<1
Setting (Low forward power)/ P>1
Setting (Overpower):
4…300.0 W
(1 A, 100 V/120 V)
16…1200.0 W
(1 A, 380 V/480 V)
20…1500.0 W
(5 A, 100 V/120 V)
80…6000.0 W
(5 A, 380 V/480 V)
Equivalent Range in %Pn 2%…157%
Power 1 Time Delay: 0.00…100.0 s
Power 1 DO Timer:
0.00…100.0 s
P1 Poledead Inh:
Disabled/Enabled
Power 2 as Power 1
Sensitive/reverse/low
forward/overpower
Operating mode:
Generating
Motoring
Sen Power1 Func:
Reverse
Low forward
Over
Sen -P>1 Setting (Reverse Power)/Sen <P
Setting (Low Forward Power)/Sen >P Setting
(Over Power):
0.3…100.0 W
(1 A, 100/120 V)
1.20…400.0 W
(1 A, 380/480 V)
1.50…500.0 W
(5 A, 100/120 V)
6.0…2000.0 W
(5 A, 380/480 V)
Equivalent range in %Pn 0.5%…157%
Sen Power 1 Delay: 0.00…100.0 s
Power 1 DO Timer: 0.00…100.0 s
P1 Poledead Inh: Disabled/Enabled
Comp angle
θ
C: -5
°
…+5.0
°
Sen Power2 as Sen Power 1
Phase overcurrent (overcurrent)
Phase O/C: Sub Heading
I>1 Function:
Disabled
DT
IEC S Inverse
IEC V Inverse
IEC E Inverse
UK LT Inverse
UK Rectifier
RI
IEEE M Inverse
IEEE V Inverse
IEEE E Inverse
US Inverse
US ST Inverse
I>1 Direction:
Non-Directional
Directional Fwd
Directional Rev
I>1 Current Set: 0.08…4.00 In
I>1 Time Delay: 0.00…100.00 s
I>1 TMS: 0.025…1.200
I>1 Time Dial: 0.01…100.00
I>1 K (RI): 0.10…10.00
I>1 Reset Char: DT/Inverse
I>1 tRESET: 0.00…100.00 s
I>2 as I>1
I>3 Status: Disabled/Enabled
I>3 Direction:
Non-Directional
Directional Fwd
Directional Rev
I>3 Current Set: 0.08…10.00 In
I>3 Time Delay: 0.00…100.00 s
I>4 as I>3
I> Char Angle: -95…+95
o
I >Function Link:
Bit 0 = VTS Blocks I>1
Bit 1 = VTS Blocks I>2
Bit 2 = VTS Blocks I>3
Bit 3 = VTS Blocks I>4
Bit 4, 5, 6 & 7 are not used
Binary function link string, selecting which
overcurrent elements (stages 1 to 4) will be
blocked if VTS detection of fuse failure
occurs.
Inverse time (IDMT) characteristic
IDMT characteristics are selectable from a
choice of four IEC/UK and five IEEE/US curves
as shown in the table below.
The IEC/UK IDMT curves conform to the
following formula:
t = T x
⎝⎜
⎜⎛
⎠⎟
⎟⎞
K
(
Ι
/
Ι
s)
α
- 1
+ L
Summary of Contents for ALSTOM P341
Page 3: ......
Page 4: ...0 0 12 3 12 3 4...
Page 5: ......
Page 6: ...00 01 1 2 33 1 3 30 30 4...
Page 7: ...0 1 2 0 0 3 4 5 2 12 3 4 6 3 5 1 0 3 0...
Page 8: ...0 10 2 0 13 4 2 1 2 3 5 6 6 7 8 8 7 6 9...
Page 9: ...0 1 2 3 3 234 34 5 6 5 75 8 9...
Page 10: ...01 21 3 1 4 56 1 0 31 0 31 0 31 7 8 6 9 1 2 3 31 121 7 9 8 6...
Page 61: ......