663
Holiday period 3
HC3/P: Last day
-------
662
Holiday period 4
HC3/P: First day
-------
663
Holiday period 4
HC3/P: Last day
-------
662
Holiday period 5
HC3/P: First day
-------
663
Holiday period 5
HC3/P: Last day
-------
662
Holiday period 6
HC3/P: First day
-------
663
Holiday period 6
HC3/P: Last day
-------
662
Holiday period 7
HC3/P: First day
-------
663
Holiday period 7
HC3/P: Last day
-------
662
Holiday period 8
HC3/P: First day
-------
663
Holiday period 8
HC3/P: Last day
-------
668
Holiday operating
level HC3/P
Frost
Heat circuit 1
Line no.
Data point
Value
Unit
700
Operating mode heat
circuit 1
Protection
710
Room temperature
Comfort setpoint HC1
21 °C
712
Room temp reduced
setpoint heat circuit 1
16 °C
714
Room temp frost
protection setpoint
HC1
10 °C
716
Comfort setpoint max
heating circuit 1
35 °C
720
Heating curve 1 slope
3.2
721
Heating curve
parallel displacement
HC1
0 °C
726
Heating curve
adaptation heat
circuit 1
Off
730
Summer/winter
changeover temp
heat circuit 1
18 °C
732
24-hour heating limit
HC1
-3 °C
740
Flow temp min
limitation heat circuit
1
8 °C
Set to required minimum
flow temperature
741
Flow temp max
limitation heat circuit
80 °C
Set to required maximum
heating flow temperature