1
750
Room temp gain
factor heat circuit 1
20 %
760
Room temperature
limitation heating
circuit 1
1 °C
770
Room temp setpoint
boost HC1 (boost
heating)
5 °C
780
Quick setback heat
circuit 1
Down to reduced setp
790
Optimum start
control max forward
shift HC1
00:00 h:m
791
Optimum stop
control max forward
shift HC1
00:00 h:m
800
Start reduced room
temp setpoint
increase HC1
------- °C
801
End reduced room
temp setpoint
increase HC1
-15 °C
820
Pump heating circuit
overtemp protection
HC1
On
830
Mixing valve setpoint
boost heating circuit
1
5 °C
832
Actuator control
mode heat circuit 1
Three-position
833
Actuator switching
differential heat
circuit 1
2 °C
834
Actuator running
time heat circuit 1
120 s
835
P-band (Xp) heat
circuit 1
32 °C
836
Integral action time
(Tn) heat circuit 1
120 s
850
Flooring plaster dry
up function HC1
Off
851
Floor setpoint
manually HC1
25 °C
861
Overtemperature
drop heating circuit 1
Always
870
Heating circuit 1 with
buffer
Yes
872
Heating circuit 1 with
precontr/primary
pump
Yes
900
Operating mode
changeover heating
circuit 1
Protection