© MHG Heating Ltd
74
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR
Telephone 08456 448802 Fax 08456 448803 Email
Web www.mhgheating.co.uk
010711
time return temp
limitation
3571
P-band (Xp) return
temp limitation
32 °C
3572
Integral action time
(Tn) return temp
limitation
120 s
3590
Min temp differential
hydraulic balancing
2 °C
Solar
Line no.
Data point
Value
Unit
3810
Temp differential on
solar
8 °C
3811
Temp differential off
solar
4 °C
3812
Min charging
temperature DHW
storage tank
------- °C
3813
Temperature
differential ON
buffer
------- °C
3814
Temperature
differential OFF
buffer
------- °C
3815
Min charging
temperature buffer
------- °C
3816
Temperature
differential
swimming pool ON
------- °C
3817
Temperature
differential
swimming pool OFF
------- °C
3818
Min charging
temperature
swimming pool
------- °C
3822
Charging priority
storage
DHW storage tank
3825
Charging time
relative priority
------- min
3826
Wait time relative
priority
5 min
3827
Wait time parallel
operation
------- min
3828
Start delay secondary
pump
60 s
3830
Collector Start
function
------- min
3831
Min collector pump
running time
20 s
3832
Collector Start
function on
07:00 h:m
3833
Collector Start
function off
19:00 h:m
3834
Collector Start
-------
min/°C