Mixing valve cooling
circuit 1 in heating
mode
Controlled
946
Locking time dew
point limit CC1
60 min
947
Flow boost hygrostat
cooling circuit 1
10 °C
948
Flow setp incr start at
rel Humidity CC1
60 %
950
Flow temp diff
dewpoint
2 °C
962
Cooling circuit 1 with
buffer
No
963
Cooling circuit 1 with
precontr/primary
pump
No
969
Operating mode
changeover cooling
circuit 1
Off
Heat circuit 2
Line no.
Data point
Value
Unit
1000
Operating mode heat
circuit 2
Automatic
1010
Room temperature
Comfort setpoint HC2
20 °C
1012
Room temp reduced
setpoint heat circuit 2
16 °C
1014
Room temp frost
protection setpoint
HC2
10 °C
1016
Comfort setpoint max
HC2
35 °C
1020
Heating curve 2 slope
3.2
1021
Heating curve
parallel displacement
HC2
0 °C
1026
Heating curve
adaptation heat
circuit 2
Off
1030
Summer/winter
changeover temp
heat circuit 2
18 °C
1032
24-hour heating limit
HC2
-3 °C
1040
Flow temp min
limitation heat circuit
2
8 °C
Set to required minimum
flow temperature
1041
Flow temp max
limitation heat circuit
2
80 °C
Set to required maximum
heating flow temperature
1050
Room temp gain
factor heat circuit 2
20 %
1060
Room temperature
limitation heating
1 °C