H1 pump DHW
charging priority
Yes
2010
Pump H1
overtemperature
drop
On
2012
H1 pump with buffer
Yes
2014
H1 pump with
precontr/primary
pump
Yes
2015
H1 Refrigeration
request
2-pipe system cooling
2033
H2 pump DHW
charging priority
Yes
2035
Pump H2
overtemperature
drop
On
2037
H2 pump with buffer
Yes
2039
H2 pump with
precontr/primary
pump
Yes
2040
H2 Refrigeration
request
2-pipe system cooling
Swimming pool
Line no.
Data point
Value
Unit
2055
Pool setpoint solar
heating
26 °C
2056
Pool setpoint
producer heating
22 °C
2065
Pool charging priority
solar
No
2070
Pool temperature
maximum
32 °C
2080
Pool with solar
Yes
Precontroller/primary
pump
Line no.
Data point
Value
Unit
2110
Flow temp min
limitation
precontroller
8 °C
2111
Flow temp max
limitation
precontroller
80 °C
2112
Flow temp min
limitation cooling
precontroller
8 °C
2130
Mixing valve setpoint
boost precontroller
10 °C
2131
Mixing valve decrease
precontroller
0 °C
2132
Actuator control
mode precontroller
Three-position
2133
Actuator switching
2
°C