3 QUICK START CONFIGURATION
The following guide gives a simple, quick start introduction to configuring the WCM5100
for Normal Mode operation as shown in section 2.1
3.1 Cold Start the Unit
When a WCM5100 is shipped from the factory it will be in the default condition, however
with previously used equipment this may not be the case. To return the unit to the default
state will require a power cycle and configuration of the bit switches.
The underside of the WCM5100 has a set of accessible bit switches and a label as shown
below:
To cold start the unit, first set bit switch 8 (Cold Start) to the OFF (Factory Default)
position. Power up the WCM5100, wait for the Status LED to come on in any state, and
then power down. To return to normal mode, return bit switch 8 to the ON ( Normal
Operation ) position. Ensure all other bit switches are in the default positions as shown on
the label. Power up the unit which will now return to the factory default state.