PE conductor resistance measurement procedure
Select the
Rpe
function using the function selector switch.
Set sub-function to
Rpe
or
Rpe(rcd)
using
UP / DOWN
keys.
Select test
parameters
(optional).
Connect
test cable to the instrument.
Connect
test leads to the item to be tested (see
Press the
TEST
key to perform the measurement.
Store
the result by pressing the
MEM
key (optional).
Figure 5.40: Examples of PE conductor resistance measurement result
Displayed results:
R
.............. PE conductor resistance
Notes:
High fluctuations of mains voltage can influence the measurement results (the noise sign
is displayed in the message field). In this case it is recommended to repeat few
measurements to check if the readings are stable.
This measurement will trip-out the RCD in RCD-protected electrical installation if test
Rpe is selected.
Select Rpe(rcd) measurement to prevent trip-out of RCD in RCD protected installation.