MI 3100 s, MI 3100 SE
Eurotest
EASI
Measurements
48
Note:
High fluctuations of mains voltage can influence the measurement results (the noise sign
is displayed in the message field). In this case it is recommended to repeat few
measurements to check if the readings are stable.
5.6.2 Voltage drop
The voltage drop is calculated based on the difference of line impedance at connection points
(sockets) and the line impedance at the reference point (usually the impedance at the
switchboard).
Circuits for measurement of voltage drop
Figure 5.30: Phase-neutral or phase-phase voltage drop measurement
– connection of plug
commander and 3-wire test lead
Voltage drop measurement procedure
Step 1:
Measuring the impedance Zref at origin
Select the
Zline
function using the function selector switch.
Set sub-function to
ΔU
using
UP / DOWN
keys.
Select test
parameters
(optional).
Connect
test cable to the instrument.
Connect
the test leads to the origin of electrical installation (see
Press the
CAL
key to perform the measurement.
Step 2:
Measuring the voltage drop
Set sub-function to
ΔU
using
UP / DOWN
keys.
Select test
parameters
(Fuse type must be selected).
Connect
test cable or plug commander to the instrument.
Connect
the test leads to the tested points (see
Press the
TEST
key to perform the measurement.
Store
the result by pressing the
MEM
key (MI 3100 SE only).