MI 3100 s, MI 3100 SE
Eurotest
EASI
Measurements
50
5.7
Earth resistance
Earth resistance is one of the most important parameters for protection against electric shock.
Main earthing arrangements, lightning systems, local earthings, soil resistivity etc can be
verified with the earthing resistance test. The measurement conforms to the EN 61557-5
standard.
The Earth resistance main function is 3-wire earth resistance test method for standard earth
resistance tests with two earthing rods.
functionality.
Figure 5.32: Earth resistance
Test parameters for earth resistance measurement
Test
Test configuration
[EARTH RE]
Limit
Maximum resistance
[OFF, 1
÷ 5 k
]
Earth resistance measurements procedure
Select
EARTH
function using the function selector switch.
Enable and set
limit
value (optional).
Connect
test leads to the instrument.
Connect
.
Press the
TEST
key to perform the measurement.
Store
the result by pressing the
MEM
key (MI 3100 SE only).