MI 3155
Eurotest
XD
Test and measurements
130
Connection diagrams
Figure 7.47: Connection of Plug commander and 3-wire test lead
Figure 7.48: Connection for Uc(P) measurement
Measurement procedure
Enter the
Zs rcd
function.
Set test parameters / limits.
Connect test cable to the instrument.
Connect 3-wire test lead or Plug commander to the object under test, see
Connect test lead P/S to external earthed point (optional), see
Start the measurement.
Save results (optional).
Figure 7.49: Examples of Zs rcd measurement result