Eurotest
XC (2,5 kV)
Tests and measurements
77
Measurement runs immediately after entering to menu.
Save results (optional).
Figure 7.4: Examples of Voltage measurement in single-phase system
Figure 7.5: Examples of Voltage measurement in three-phase system
Measurement results / sub-results
Single-phase system
Uln
voltage between phase and neutral conductors
Ulpe
voltage between phase and protective conductors
Unpe
voltage between neutral and protective conductors
Freq
frequency
Three-phase system
U12
voltage between phases L1 and L2
U13
voltage between phases L1 and L3
U23
voltage between phases L2 and L3
Freq
frequency
Field
1.2.3
- correct connection
– CW rotation sequence
3.2.1
- invalid connection
– CCW rotation sequence
IT earthing system (selection of IT earthling system required)
U12
voltage between phases L1 and L2
U1pe
voltage between phase L1 and PE
U2pe
voltage between phase L2 and PE
Freq
frequency