MI 3152(H)
Eurotest
XC (2,5 kV)
Tests and measurements
115
7.18
Harmonics
Figure 7.61: Harmonics menu
Measurement parameters / limits
Ch1 clamp type
Current clamp adapter
[A1018, A1019, A1391]
Range
Range for selected current clamp adapter
A1018 [20 A]
A1019 [20 A]
A1391 [40 A, 300 A]
Limit(THDu)
Max. THD of voltage
[3 % ... 10 %]
Connection diagram
Figure 7.62: Harmonics measurement
Measurement procedure
Enter the
Harmonics
function.
Set parameters / limits.
Connect voltage test leads and current clamp to the instrument.
Connect the voltage test leads and current clamp to the item to be tested, see
Figure
7.62
.
Start the continuous measurement.
Stop the measurement.
Save results (optional).