MI 3152(H)
Eurotest
XC (2,5 kV)
Appendix B
– Profile notes
166
Modified
Fuse type K
Rated
current
(A)
Disconnection time [s]
35m
0.1
0.2
0.4
Min. prospective short- circuit current (A)
0.5
9.4
9.4
9.4
9.4
1
18.8
18.8
18.8
18.8
1.6
30
30
30
30
2
37.5
37.5
37.5
37.5
4
75
75
75
75
6
112.5
112.5
112.5
112.5
10
187.5
187.5
187.5
187.5
13
243.8
243.8
243.8
243.8
15
281.3
281.3
281.3
281.3
16
300
300
300
300
20
375
375
375
375
25
468.8
468.8
468.8
468.8
32
600
600
600
600