78
Technical Bulletin—TC-9100 Universal Controller
PM Tag
Type
Alg. Tag Description
PMxK1
Number
LSP
Local Set Point
PMxI1@
Connection PV@
Process Variable Source
PMxI2@
Connection RS@
Remote Set Point Source
PMxI3@
Connection RV@
Reference Variable Source
PMxTYP
2 Bytes
TYP
Algorithm Options
X5...X1
Algorithm 2 (00010)
X6=1
Enable Low Limit (Anti-freeze) Override
X7=1
Enable Summer Compensation
X8=1
Enable Winter Compensation
X9=1
Enable Shutoff & OFF Override
X10=1
Enable Manual OFF Fan Override
X11=1
Enable Startup Override
X12=0
Startup Out Level = 0% or Low Limit value,
whichever is lower
X12=1
Startup Out Level = 100%
X13=1
OVR
Enable Air Quality Override
X14=0
Air Quality Override Out Level = 0% or Low
Limit value, whichever is lower
X14=1
Air Quality Override Out Level = 100%
X15=1
Enable Reverse Action
X16=0
0.1% Error Dead Band
X16=1
1% Error Dead Band
PMxK2 Number
PB Proportional
Band
PMxK3
Number
TI
Integral (Reset) Timing
PMxK4 Number
HIL
Upper
Limit of the Control Output
PMxK5 Number
LOL
Lower
Limit of the Control Output
PMxK6
Number
BSB
Set Point Bias During STANDBY
PMxK7
Number
BNT
Set Point Bias During NIGHT
Algorithm 2:
PI Controller