70
Technical Bulletin—TC-9100 Universal Controller
Item Type MEM R/W Tag Description
Hex Dec
78
120 1 Byte
D
WP OCN3
Output 3 Configuration
X5...X1
Source of Module in binary code
(Numeric Items 0A to 0F, e.g., 0A =
01010)
X8...X6
Output
Type
=000
output
not
used
=011
On/Off
Output
=100
DAT
Output
=101
PAT Output (also uses Output 4)
=110
2-Stage On/Off (also uses Output 4)
79
121 Number
D
WP OCO3
PAT/DAT Timing or Load Rating for
Output Module 3
7A
122 1 Byte
D
WP OCN4
Output 4 Configuration
X5...X1
Source of Module in binary code
(Numeric Items 0A to 0F, e.g., 0A =
01010)
X8...X6
Output
Type
=000
output not used (or used with Output 3)
=011
On/Off
Output
7B
123 Number
D
WP OCO4
PAT Dead Band or 2-Stage
Differential for Output 3
7C
124 1 Byte
D
WP OCN5
Output 5 Configuration
X5...X1
Source of Module in binary code
(Numeric Items 0A to 0F, e.g., 0A =
01010)
X8...X6
Output
Type
=000
output
not
used
=011
On/Off
Output
=100
DAT
Output
=101
PAT Output (also uses Output 6)
=110
2-Stage On/Off (also uses Output 6)
=111
3-Speed Fan Control (also uses
Outputs 6 and 7)
7D
125 Number
D
WP OCO5
PAT/DAT Timing, Load Rating for
Output Module 5, or Fan Speed Break
Point 1