Technical Bulletin—TC-9100 Universal Controller
47
Item Tag
(Cont.)
Item Address
(Hex/Dec)
Description
MSK 21/33
Outputs – Supervisory Control Enable
DO3E
Bit 1
1 = Enable Digital Output 3 for Supervisory Control.
DO4E
Bit 2
1 = Enable Digital Output 4 for Supervisory Control.
DO5E
Bit 3
1 = Enable Digital Output 5 for Supervisory Control.
DO6E
Bit 4
1 = Enable Digital Output 6 for Supervisory Control.
DO7E
Bit 5
1 = Enable Digital Output 7 for Supervisory Control.
DO1E
Bit 6
1 = Enable Digital Output 1 for Supervisory Control.
DO2E
Bit 7
1 = Enable Digital Output 2 for Supervisory Control.
ODC 22/34
Outputs – Supervisory Control Command
DO3C
Bit 1
1 = Set Digital Output 3 On if DO3E = 1.
0 = Set Digital Output 3 Off if DO3E = 1.
DO4C
Bit 2
1 = Set Digital Output 4 On if DO4E = 1.
0 = Set Digital Output 4 Off if DO4E = 1.
DO5C
Bit 3
1 = Set Digital Output 5 On if DO5E = 1.
0 = Set Digital Output 5 Off if DO5E = 1.
DO6C
Bit 4
1 = Set Digital Output 6 On if DO6E = 1.
0 = Set Digital Output 6 Off if DO6E = 1.
DO7C
Bit 5
1 = Set Digital Output 7 On if DO7E = 1.
0 = Set Digital Output 7 Off if DO7E = 1.
DO1C
Bit 6
1 = Set Digital Output 1 On if DO1E = 1.
0 = Set Digital Output 1 Off if DO1E = 1.
DO2C
Bit 7
1 = Set Digital Output 2 On if DO2E = 1.
0 = Set Digital Output 2 Off if DO2E = 1.
Certain configuration rules must be followed to enable the controller to
operate correctly with the room command module. All features of the
room command module are available, except for the viewing and setting
of set points and biases for the operating modes of the controller, which
are reserved for the TC-9102 controller only.
The room temperature process variable must be configured as AI1. The
room command module will automatically write the value of the room
temperature into AI1 (Item 01), unless Bit 3 of Item TCS2 (85 Hex / 133
Dec) is set to “1”, in which case a TS-9100 or
RS-1100
series sensor
(with a 0-10V output) must be physically connected to the input terminals
for AI1 (25, 50, 52).
The remote room set point must be configured as AI2. The room
command module will automatically write the value of the room set point
into AI2 (Item 02). The controller will ignore a remote set point device
connected to the input terminal for AI2 (26, 50, 52) when the TM-9180
Room Command Module is connected.
If it is desired to display the outdoor temperature on the room command
module, then the supervisory system must periodically write the value of
the outdoor temperature in °C to External Analog Input 4 (XAI4 Item 19
Hex / 25 Decimal) and update the value after a power interruption.
The heating symbol on the room command module is displayed when the
output of Programmable Module 1 is greater than 5%. Therefore,
Programmable Module 1 must be configured as the main heating
controller for the room.
Configuration
for a TM-9180
Room
Command
Module