11. Tables
Attention: the type and cross section of the connecting cables must be chosen according
to their operating current and laying must be as established by existing laws; this is the
responsibility of the installer. The UPS input current and output power are given in paragraph
2.4 and the battery current in Table 7.
Warning: The following tables give only an indication of the cable cross sections to use as far
as concerns using unipolar cables, without sheath, in PVC and laid in a pipe above ground.
Tabella 1
Sezioni cavi minime raccomandate per UPS ARCHIMOD
®
Minimal Recommended Cable Sections for UPS ARCHIMOD
®
Potenza
Power
Fasi Ingresso
Input Phases
Fasi Uscita
Output Phases
Cavo Ingresso
Input Cable
Cavo Uscita
Output Cable
Input I
max
20 kVA
3
3
5 x (10 mm
2
)
5 x (10 mm
2
)
37 A
1
1
3 x (25 mm
2
)
3 x (25 mm
2
)
111 A
1
3
3 x (25 mm
2
)
5 x (10 mm
2
)
111 A
3
1
5 x (25 mm
2
)
3 x (25 mm
2
)
111 A
40 kVA
3
3
5 x (25 mm
2
)
5 x (25 mm
2
)
74 A
60 kVA
3
3
5 x (35 mm
2
)
5 x (35 mm
2
)
111 A
80 kVA
3
3
5 x (50 mm
2
)
5 x (50 mm
2
)
148 A
100 kVA
3
3
5 x (70 mm
2
)
5 x (70 mm
2
)
185 A
120 kVA
3
3
5 x (95 mm
2
)
5 x (95 mm
2
)
222 A
Tabella 2
Valori fusibili batteria raccomandati
UPS ARCHIMOD
®
Recommended Battery Fuse Ratings
Potenza - Power
Fusibile di batteria - Battery fuse
UPS ARCHIMOD
®
F B+
F B-
20 kVA
1 x 100A 500V aR (22 x 58)
1 x 100A 500V aR (22 x 58)
40 kVA
2 x 100A 500V aR (22 x 58)
2 x 100A 500V aR (22 x 58)
60 kVA
3 x 100A 500V aR (22 x 58)
3 x 100A 500V aR (22 x 58)
Tabella 3
Valori fusibili batteria raccomandati per UPS ARCHIMOD
®
BATTERY/2
UPS ARCHIMOD
®
BATTERY/2 Recommended Battery Fuse Ratings
Potenza - Power
Fusibile di batteria - Battery fuse
ARCHIMOD
®
BATTERY
F B+
F B-
20 kVA
N.1 - 100A 500V aR (22 x 58)
N.1 - 100A 500V aR (22 x 58)
40 kVA
N.2 - 100A 500V aR (22 x 58)
N.2 - 100A 500V aR (22 x 58)
60 kVA
N.3 - 100A 500V aR (22 x 58)
N.3 - 100A 500V aR (22 x 58)
80 kVA
N.4 - 100A 500V aR (22 x 58)
N.4 - 100A 500V aR (22 x 58)
100 kVA
N.5 - 100A 500V aR (22 x 58)
N.5 - 100A 500V aR (22 x 58)
120 kVA
N.6 - 100A 500V aR (22 x 58)
N.6 - 100A 500V aR (22 x 58)